1. A 3phase induction motor load draws a power of 13.33 KVA at 0.75pf from 460V source. If a synchronous motor with 90%pf leading is connected in parallel to the induction motor to improve the overall power factor to 80% lagging, calculate the required KW of the synchronous motor.

Electric Motor Control
10th Edition
ISBN:9781133702818
Author:Herman
Publisher:Herman
Chapter39: Synchronous Motor Operation
Section: Chapter Questions
Problem 14SQ: Induction motors and welding transformers require magnetizing current, which causes a. lagging power...
icon
Related questions
icon
Concept explainers
Question

1. A 3phase induction motor load draws a power of 13.33 KVA at 0.75pf from 460V source. If a synchronous motor with 90%pf leading is connected in parallel to the induction motor to improve the overall power factor to 80% lagging, calculate the required KW of the synchronous motor.

Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 3 steps with 3 images

Blurred answer
Knowledge Booster
Synchronous Motor
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Electric Motor Control
Electric Motor Control
Electrical Engineering
ISBN:
9781133702818
Author:
Herman
Publisher:
CENGAGE L
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning