The four-bus power system in Figure 2 has following equipment parameters: G1: 500 MVA 13.8 KV, xd"=x1=x2=0.20, x0=0.10pu G2: 750 MVA, 18 kv, xd"=x1=x2=0.18, x0=0.09pu G3: 1000 MVA, 20 kv, xd"=x1=0.17, x2=0.20, x0=0.09pu T1: 500 MVA, 13.8/500 kv, delta-wye, x=0.12pu T2: 750 MVA, 18/500 kv, delta-wye, x=0.10pu T3: 1000 MVA, 20/500 kv, delta-wye, x=0.10pu Each Line: X1 = 50 Ω; X0 = 150 Ω All per-unit reactance values are given on the respective equipment rating (voltage and power) as the base. The inductor connected to generator G3 neutral has a reactance of 0.028 Ω. (a) Draw the zero- positive- and negative-sequence reactance diagrams using a 1,000 MVA, 20 kV base in the zone of generator G3. Neglect ∆ - Y transformer phase shift. (b) Faults at bus 1 are of interest. Determine the Thevenin equivalent of each sequence network as viewed from the fault bus. Prefault voltage is 1.0 pu. Prefault load currents and ∆ - Y transformer phase shift are neglected.

Introductory Circuit Analysis (13th Edition)
13th Edition
ISBN:9780133923605
Author:Robert L. Boylestad
Publisher:Robert L. Boylestad
Chapter1: Introduction
Section: Chapter Questions
Problem 1P: Visit your local library (at school or home) and describe the extent to which it provides literature...
icon
Related questions
icon
Concept explainers
Question

The four-bus power system in Figure 2 has following equipment parameters:

G1: 500 MVA 13.8 KV, xd"=x1=x2=0.20, x0=0.10pu

G2: 750 MVA, 18 kv, xd"=x1=x2=0.18, x0=0.09pu

G3: 1000 MVA, 20 kv, xd"=x1=0.17, x2=0.20, x0=0.09pu

T1: 500 MVA, 13.8/500 kv, delta-wye, x=0.12pu

T2: 750 MVA, 18/500 kv, delta-wye, x=0.10pu

T3: 1000 MVA, 20/500 kv, delta-wye, x=0.10pu

Each Line: X1 = 50 Ω; X0 = 150 Ω

All per-unit reactance values are given on the respective equipment rating (voltage and power) as the base. The inductor connected to generator G3 neutral has a reactance of 0.028 Ω.

(a) Draw the zero- positive- and negative-sequence reactance diagrams using a 1,000 MVA, 20 kV base in the zone of generator G3. Neglect ∆ - Y transformer phase shift.

(b) Faults at bus 1 are of interest. Determine the Thevenin equivalent of each sequence network as viewed from the fault bus. Prefault voltage is 1.0 pu. Prefault load currents and ∆ - Y transformer phase shift are neglected.



T1
T3
G3
j50.0 2
j50.0 2
j50.0 2
T2
G2
Transcribed Image Text:T1 T3 G3 j50.0 2 j50.0 2 j50.0 2 T2 G2
Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 7 steps with 6 images

Blurred answer
Knowledge Booster
Fault analysis
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Recommended textbooks for you
Introductory Circuit Analysis (13th Edition)
Introductory Circuit Analysis (13th Edition)
Electrical Engineering
ISBN:
9780133923605
Author:
Robert L. Boylestad
Publisher:
PEARSON
Delmar's Standard Textbook Of Electricity
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:
9781337900348
Author:
Stephen L. Herman
Publisher:
Cengage Learning
Programmable Logic Controllers
Programmable Logic Controllers
Electrical Engineering
ISBN:
9780073373843
Author:
Frank D. Petruzella
Publisher:
McGraw-Hill Education
Fundamentals of Electric Circuits
Fundamentals of Electric Circuits
Electrical Engineering
ISBN:
9780078028229
Author:
Charles K Alexander, Matthew Sadiku
Publisher:
McGraw-Hill Education
Electric Circuits. (11th Edition)
Electric Circuits. (11th Edition)
Electrical Engineering
ISBN:
9780134746968
Author:
James W. Nilsson, Susan Riedel
Publisher:
PEARSON
Engineering Electromagnetics
Engineering Electromagnetics
Electrical Engineering
ISBN:
9780078028151
Author:
Hayt, William H. (william Hart), Jr, BUCK, John A.
Publisher:
Mcgraw-hill Education,