Concept explainers
(a)
Calculate the average power delivered by the current source of
(a)
Answer to Problem 13E
The average power delivered by the current source of
Explanation of Solution
Given data:
The value of current source
The value of impedance
Formula used:
Write the expression for average power delivered to the resistor.
Here,
Calculation:
Convert the rectangular form of the current value into polar form as follows:
Therefore, the maximum value of the current
The given value of impedance has purely resistive. Therefore, the value of R is equal to Z.
Modify equation (1) for impedance of
Substitute
Conclusion:
Thus, the average power delivered by the current source of
(b)
Calculate the average power delivered by the current source of
(b)
Answer to Problem 13E
The average power delivered by the current source of
Explanation of Solution
Given data:
The value of current source
The value of impedance
Formula used:
Write the expression for average power delivered.
Here,
Write the expression for voltage.
Here,
Calculation:
Convert the value of
Modify equation (3) for impedance of
Substitute
Therefore, the maximum value of the voltage
Modify equation (2) for impedance of
Substitute
Conclusion:
Thus, the average power delivered by the current source of
(c)
Calculate the average power delivered by the current source of
(c)
Answer to Problem 13E
The average power delivered by the current source of
Explanation of Solution
Given data:
The value of current source
The value of impedance
Calculation:
Convert the value of
Modify equation (3) for impedance of
Substitute
Therefore, the maximum value of the voltage
Modify equation (2) for impedance of
Substitute
Conclusion:
Thus, the average power delivered by the current source of
(d)
Calculate the average power delivered by the current source of
(d)
Answer to Problem 13E
The average power delivered by the current source of
Explanation of Solution
Given data:
The value of current source
The value of impedance
Calculation:
Modify equation (3) for impedance of
Substitute
Therefore, the maximum value of the voltage
Modify equation (2) for impedance of
Substitute
Conclusion:
Thus, the average power delivered by the current source of
(e)
Calculate the average power delivered by the current source of
(e)
Answer to Problem 13E
The average power delivered by the current source of
Explanation of Solution
Given data:
The value of current source
The value of impedance
Calculation:
Convert the value of
Modify equation (3) for impedance of
Substitute
Therefore, the maximum value of the voltage
Modify equation (2) for impedance of
Substitute
Conclusion:
Thus, the average power delivered by the current source of
Want to see more full solutions like this?
Chapter 11 Solutions
Loose Leaf for Engineering Circuit Analysis Format: Loose-leaf
- If a 3- Ø, Y-connected system has a line-to-line voltage of 1103Sin(377t) V, then the line-to-neutral (RMS) voltage would be:arrow_forwardProblem 11.34. At full load, a commercially available 106 hp, three-phase induction motor operates at an efficiency of 96% and a power factor of 0.87 lag. The motor is supplied from a three-phase outlet with a line-voltage rating of 208 V. 1. What is the magnitude of the line current in Ampere drawn from the 208 V outlet? (1 hp = 746 W). 2. Calculate the reactive power in kVAR supplied to the motor.arrow_forwardf. A residential air conditioning unit with an SEER of 14 serves a single-detached family residence in Quezon City, Philippines having an annual cooling load hours of 6,116 hours. The total cooling load is 36,000 Btu/hr. Calculate the annual operating cost for the A/C unit if the energy cost is Php 7.96/kW-hr.arrow_forward
- At full load, a commercially available 100 hp, three-phase induction motor operates at an efficiency of 97% and a power factor of 0.88 lag. The motor is supplied from a three-phase outlet with a linevoltage rating of 208 V. 1. a) What is the magnitude of the line current drawn from the 208 V outlet? (1 hp=746 W.) 2. b) Calculate the reactive power supplied to the motor.arrow_forwardA transmission line of impedance (0.05 + j0.02) pu interconnects the buses of a switchyard and a bulk supply point. The receiving end apparent power is (1.0 + j0.6) pu and sending end voltage, 1/0°pu. Estimate the following: i) Receiving end voltage after two iterations ii) Perform two further iterations to test the convergence of the value of receiving end voltage deduced in (i) iii) load currentarrow_forwardGiven a mesh connected system with reactive factor of 60 percent and true power of 2,500 kW. Calculate the reactive powerarrow_forward
- Derive the relationship for maximum power Eb = v/2arrow_forwardA transmission line delivers 1200MW at 500kV and 85% power factor. The series impedance of the line is 0.42 + j0.65 ohms/mi and the shunt impedance to.neutral is -j0.12 x 10^6 ohms-mi. What is the velocity propagation of the line. A. 560 × 10^6 km/hr B. 890 × 10^6 km/hr C. 750 × 10^6 km/hr D. 510 × 10^6 km/hrarrow_forwardA transmission line has generalized circuit constants are A=0.93+j0.016,B=20+j140.The load at the receiving end is 60MVA, 50HZ, 0.8 power factor lagging. The voltage at the supply end is 132KV. Caluclate the load voltage and voltage regulation,Use nominal-π approximation.arrow_forward
- A series generator delivers a power of 6.25kW and a load resistance of25Ω. If RA=0.05Ω and RS=0.025Ω, calculate the generated emf.arrow_forwardA 3-phase, 50 Hz, 440 V motor develops 100 H.P, which works for 3000 hours per annum, the power factor being 0·75 lagging and efficiency 93%. A bank of capacitors is connected in delta across the supply terminals and power factor raised to 0·95 lagging. The tariff is Rs 100 per kVA plus 20 paise per kWh. If the power factor is improved to 0·95 lagging by capacitors costing Rs 60 per kVAR and having a power loss of 100 W per kVA. Compute the annual saving effected. Allow 12% per annum for interest and depreciation on capacitorsarrow_forward. A power station has a connected load of 48 MW. The energy generated for the year is 61,500 MWh. If the station has a load factor of 35%, solve the demand factor of the station. Answer: 0.4179 or 41.79% Subject: Distribution System and Substation Designarrow_forward
- Introductory Circuit Analysis (13th Edition)Electrical EngineeringISBN:9780133923605Author:Robert L. BoylestadPublisher:PEARSONDelmar's Standard Textbook Of ElectricityElectrical EngineeringISBN:9781337900348Author:Stephen L. HermanPublisher:Cengage LearningProgrammable Logic ControllersElectrical EngineeringISBN:9780073373843Author:Frank D. PetruzellaPublisher:McGraw-Hill Education
- Fundamentals of Electric CircuitsElectrical EngineeringISBN:9780078028229Author:Charles K Alexander, Matthew SadikuPublisher:McGraw-Hill EducationElectric Circuits. (11th Edition)Electrical EngineeringISBN:9780134746968Author:James W. Nilsson, Susan RiedelPublisher:PEARSONEngineering ElectromagneticsElectrical EngineeringISBN:9780078028151Author:Hayt, William H. (william Hart), Jr, BUCK, John A.Publisher:Mcgraw-hill Education,