Chapter 12, Problem 1RQ
To determine

The average amount of current flowing in two remaining phases.

Expert Solution & Answer
Check Mark

Explanation of Solution

Given:

The name plate current of three-phase motor is 56 A.

Calculation:

A failure phase occurs when power is lost from a three-phase motor power supply line. The motor is still running, but it draws excessive current. This phenomenon is known as Single phasing. Single phasing causes a current increase of 173% in average of both phases which remain energized in a three-phase motor.

Calculate the current flowing in two remaining phases:

  Iavg=173%ofI=173100×I=1.73×56A=96.88A

Thus, the average amount of current flowing in two remaining phases is 96.88A_.

Want to see more full solutions like this?

Subscribe now to access step-by-step solutions to millions of textbook problems written by subject matter experts!
Knowledge Booster
Background pattern image
Mechanical Engineering
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, mechanical-engineering and related others by exploring similar questions and additional content below.
Recommended textbooks for you
Text book image
Understanding Motor Controls
Mechanical Engineering
ISBN:9781337798686
Author:Stephen L. Herman
Publisher:Delmar Cengage Learning
Text book image
Electrical Transformers and Rotating Machines
Mechanical Engineering
ISBN:9781305494817
Author:Stephen L. Herman
Publisher:Cengage Learning