measurements of three-phase voltage and current samples obtained from the PSCAD/EMTDC. Fig. 8 depicts the 220 kV, 50 Hz simulated system one-line diagram. The other related parameters of the simulated system are shown in Table 1, transmission lines are assumed completely transposed. Fig. 9 & 10 show 3ph voltages and currents waveforms for 3ph to ground fault at 50% of the second line without and with UPFC respectively. It is clear that when UPFC is involved in the fault loop, the the voltage and current signals would be deviated from the actual value.

Fig. 8. Transmission system with UPFC.

Table 1. Parameters of simulated transmission system.

Length of transmission line 200Km
Source 1 100MVA
Phase angle 1 10 degree
Source 2 100MVA
Phase …show more content…

Estimated output of RNN for classification level

Fault type & location Phase A Phase B Phase C Ground Desired Actual Desired Actual Desired Actual Desired Actual
A-G at 25%1st line 1 0.9999 0 0.0036 0 0.0001 1 0.9909
A-G at 85%1st line 1 0.9999 0 0.7411 0 0.04 1 0.9995
A-G at 25%2nd line 1 0.9999 0 0.0152 0 0.008 1 0.9974
A-G at 85%2nd line 1 0.9977 0 0.0044 0 0.0111 1 0.9978
A-B at 25%1st line 1 0.9147 1 0.9999 0 0.0033 0 0.8744
A-B at 85%1st line 1 0.9899 1 0.9999 0 0.0002 0 0.0026
A-B at 25%2nd line 1 0.9999 1 0.9999 0 0.007 0 0.0018
A-B at 85%2nd line 1 0.9999 1 0.9999 0 0.0033 0 0.0085
AB-G at 25%1st line 1 0.9993 1 0.999 0 0.0207 1 0.9962
AB-G at 85%1st line 1 0.9888 1 0.9991 0 0.0001 1 0.9958
AB-G at 25%2nd line 1 0.9796 1 0.9999 0 0.0005 1 0.9973
AB-G at 85%2nd line 1 0.9996 1 0.9999 0 0.0038 1 0.9914
ABC-G at 25%1st line 1 0.9999 1 0.8519 1 0.9794 1 0.9902
ABC-G at 85%1st line 1 0.9999 1 0.9999 1 0.9992 1 0.3318
ABC-G at 25%2nd line 1 0.8739 1 0.6861 1 0.9999 1 0.9999
ABC-G at 85%2nd line 1 0.9999 1 0.9999 1 0.9978 1 0.9111

Table 6. Estimated output of GP for detection