2. A 120 V, 60 Hz voltage is supplied to a circuit with an apparent power of 750 VÀ and a Power Factor of .8 lagging. How much reactive power required to correct the Power Factor to 1? -450 VAR 450 VAR 600 VAR -600 VAR

Delmar's Standard Textbook Of Electricity
7th Edition
ISBN:9781337900348
Author:Stephen L. Herman
Publisher:Stephen L. Herman
Chapter23: Resistive-inductive-capacitive Series Circuits
Section: Chapter Questions
Problem 2PP: The circuit is connected to a 400-Hz line with an applied voltage of 35.678 V. The resistor has a...
icon
Related questions
Question
2. A 120 V, 60 Hz voltage is supplied to a circuit
with an apparent power of 750 VA and a Power
Factor of .8 lagging. How much reactive power is
required to correct the Power Factor to 1?
-450 VAR
450 VAR
600 VAR
-600 VAR
Transcribed Image Text:2. A 120 V, 60 Hz voltage is supplied to a circuit with an apparent power of 750 VA and a Power Factor of .8 lagging. How much reactive power is required to correct the Power Factor to 1? -450 VAR 450 VAR 600 VAR -600 VAR
Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 2 steps with 1 images

Blurred answer
Knowledge Booster
Three Phase Transformer
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Delmar's Standard Textbook Of Electricity
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:
9781337900348
Author:
Stephen L. Herman
Publisher:
Cengage Learning