6. A 3-phase AC generator is supplying power to a load of 3200kW at 2300V and a power factor of 60%. Assume that the loss of the line, the generator armature and the load is equal to 10% of the load, what would be the savings in watts if the power factor were raised to 80%. c. 80,000 a. 100,000 b. 140,000 d. 230,000

Electricity for Refrigeration, Heating, and Air Conditioning (MindTap Course List)
10th Edition
ISBN:9781337399128
Author:Russell E. Smith
Publisher:Russell E. Smith
Chapter7: Alternating Current, Power Distribution, And Voltage Systems
Section: Chapter Questions
Problem 8RQ
icon
Related questions
Question
6. A 3-phase AC generator is supplying power to a load of 3200kW at 2300V and a power factor of
60%. Assume that the loss of the line, the generator armature and the load is equal to 10% of the load, what
would be the savings in watts if the power factor were raised to 80%.
c. 80,000
a. 100,000
b. 140,000
d. 230,000
Transcribed Image Text:6. A 3-phase AC generator is supplying power to a load of 3200kW at 2300V and a power factor of 60%. Assume that the loss of the line, the generator armature and the load is equal to 10% of the load, what would be the savings in watts if the power factor were raised to 80%. c. 80,000 a. 100,000 b. 140,000 d. 230,000
Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 3 steps with 2 images

Blurred answer
Knowledge Booster
Synchronous Generator
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Electricity for Refrigeration, Heating, and Air C…
Electricity for Refrigeration, Heating, and Air C…
Mechanical Engineering
ISBN:
9781337399128
Author:
Russell E. Smith
Publisher:
Cengage Learning