A 30 MVA, three-phase, wye-connected, 60 Hz, 13.8 kV synchronous alternator has negligible stator resistance and synchronous reactance of 10 W/phase.   Calculate the % voltage regulation of the alternator when it is operation in isolation (stand-alone) and delivering rated MVA to a 0.866 pf leading load at 13.8 kV.  Calculate the % voltage regulation of the alternator when it is operation in isolation (stand-alone) and delivering rated MVA to a 0.707 pf lagging load at 13.8 kV.

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter12: Power System Controls
Section: Chapter Questions
Problem 12.13P
icon
Related questions
Question

A 30 MVA, three-phase, wye-connected, 60 Hz, 13.8 kV synchronous alternator has negligible stator resistance and synchronous reactance of 10 W/phase.

 

  • Calculate the % voltage regulation of the alternator when it is operation in isolation (stand-alone) and delivering rated MVA to a 0.866 pf leading load at 13.8 kV. 
  • Calculate the % voltage regulation of the alternator when it is operation in isolation (stand-alone) and delivering rated MVA to a 0.707 pf lagging load at 13.8 kV. 

 

Expert Solution
steps

Step by step

Solved in 2 steps with 2 images

Blurred answer
Knowledge Booster
Synchronous Generator
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning