A 6 pole, 3 phase, 50 Hz alternator has 12 slots per pole and 4 conductors per slot. The winding is five-sixth pitch and the flux per pole is 1.5 wb.  The armature coils are all connected in series with star connection. Calculate  the induced emf per phase

Delmar's Standard Textbook Of Electricity
7th Edition
ISBN:9781337900348
Author:Stephen L. Herman
Publisher:Stephen L. Herman
Chapter31: Three-phase Alternators
Section: Chapter Questions
Problem 1RQ: What conditions must be met before two alternators can be paralleled together?
icon
Related questions
Question

A 6 pole, 3 phase, 50 Hz alternator has 12 slots per pole and 4 conductors per slot. The winding is five-sixth pitch and the flux per pole is 1.5 wb.  The armature coils are all connected in series with star connection. Calculate  the induced emf per phase. [Ans. Emf = 14730 volts = 14.73 kV] 