equivalent series impedance 62 + j388 mN referred to the low-voltage winding. 1. A three-phase short circuit is applied to the low-voltage winding. Calculate the voltage applied to the high-voltage winding which will result in rated current into the short circuit. o. The short circuit is removed and a three-phase load is connected to the low-voltage winding. With rated voltage applied to the high-voltage winding, the input power to the transformer is observed to be 18 MW at 0.75 power-factor lagging. Calculate the line-line terminal voltage at the load.

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter3: Power Transformers
Section: Chapter Questions
Problem 3.27P: A three-phase transformer is rated 1000MVA,220Y/22kV. The Y-equivalent short-circuit impedance,...
icon
Related questions
Question
A three-phase Y-Y transformer is rated at 25 MVA, 13.8-kV:69-kV and has a single-phase
equivalent series impedance 62 + j388 mN referred to the low-voltage winding.
a. A three-phase short circuit is applied to the low-voltage winding. Calculate the voltage applied to the
high-voltage winding which will result in rated current into the short circuit.
b. The short circuit is removed and a three-phase load is connected to the low-voltage winding. With
rated voltage applied to the high-voltage winding, the input power to the transformer is observed to
be 18 MW at 0.75 power-factor lagging. Calculate the line-line terminal voltage at the load.
Transcribed Image Text:A three-phase Y-Y transformer is rated at 25 MVA, 13.8-kV:69-kV and has a single-phase equivalent series impedance 62 + j388 mN referred to the low-voltage winding. a. A three-phase short circuit is applied to the low-voltage winding. Calculate the voltage applied to the high-voltage winding which will result in rated current into the short circuit. b. The short circuit is removed and a three-phase load is connected to the low-voltage winding. With rated voltage applied to the high-voltage winding, the input power to the transformer is observed to be 18 MW at 0.75 power-factor lagging. Calculate the line-line terminal voltage at the load.
Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 3 steps

Blurred answer
Knowledge Booster
Three Phase Transformer
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning