Ex: Consider a A/Y- Connected, 15- MVA, 33/11-KV transformer with differential protection applied, For the current transformer notes ratios Show in figure d.36. Calculate the relay currents on full load. Find the minimum relay Current setting to allow 125 percent overload. 33/11 Kv 2000/5A 300/5A mm m part M ANL ip ir m IS A

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter10: System Protection
Section: Chapter Questions
Problem 10.28P
icon
Related questions
icon
Concept explainers
Question
Ex: Consider a
A/Y - Connected, 15-MVA, 33 / 11 -KV
transformer with differential protection applied,
For the current transformer notes ratios show in
figure d.36. Calculate the relay currents on full
load. Find the minimum relay Current setting
to allow 125 percent overload.
33/11 Kv
300/5A
2000/5A
faz
m
AAAA
E
C
An
tp
ir
m
is
Transcribed Image Text:Ex: Consider a A/Y - Connected, 15-MVA, 33 / 11 -KV transformer with differential protection applied, For the current transformer notes ratios show in figure d.36. Calculate the relay currents on full load. Find the minimum relay Current setting to allow 125 percent overload. 33/11 Kv 300/5A 2000/5A faz m AAAA E C An tp ir m is
Expert Solution
steps

Step by step

Solved in 2 steps

Blurred answer
Knowledge Booster
Protection System in Power Plant
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning