"In back up protection scheme of power system a 5-Amp, 4-second overcurrent relay having a current setting of 150% and a time setting multiplier of 0.65 connected to supply circuit through a 500/5current transformer when the circuit carries a fault current of 4 kA. The relay manufacturer has provided the values of operating times for the range of PSM from 5 to 6 as 2.75 seconds. Determine the following parameters for this overcurrent relay (1) Pick-up current value (in Amp); (ii) Fault current in relay coil (in Amp); (ii) Plug setting multiplier; (iv) Actual operating time of over current relay(in second).

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter10: System Protection
Section: Chapter Questions
Problem 10.11P
icon
Related questions
icon
Concept explainers
Question
"In back up protection scheme of power system a 5-Amp, 4-second overcurrent relay having a current setting of 150% and a time setting multiplier of 0.65 connected to supply circuit through a 500/5current
transformer when the circuit carries a fault current of 4 kA. The relay manufacturer has provided the values of operating times for the range of PSM from 5 to 6 as 2.75 seconds. Determine the following
parameters for this overcurrent relay (0) Pick-up current value (in Amp); (ii) Fault current in relay coil (in Amp): (ii) Plug setting multiplier; (iv) Actual operating time of over current relay(in second).
Transcribed Image Text:"In back up protection scheme of power system a 5-Amp, 4-second overcurrent relay having a current setting of 150% and a time setting multiplier of 0.65 connected to supply circuit through a 500/5current transformer when the circuit carries a fault current of 4 kA. The relay manufacturer has provided the values of operating times for the range of PSM from 5 to 6 as 2.75 seconds. Determine the following parameters for this overcurrent relay (0) Pick-up current value (in Amp); (ii) Fault current in relay coil (in Amp): (ii) Plug setting multiplier; (iv) Actual operating time of over current relay(in second).
Expert Solution
steps

Step by step

Solved in 5 steps with 3 images

Blurred answer
Knowledge Booster
Protection System in Power Plant
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning