Problem 4.4: A 3-phase, Y-connected synchronous generator is rated 15 MVA, 13.8 kV. Its resistance is negligible, and the synchronous reactance is 2 Q/ ph. Dcterminc the field excitation voltage E, when delivering rated MVA at 0.90 power factor lagging.

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter6: Power Flows
Section: Chapter Questions
Problem 6.48P
icon
Related questions
icon
Concept explainers
Question
Problem 4.4: A 3-phase, Y-connected synchronous generator is rated 15 MVA,
13.8 kV. Its resistance is negligible, and the synchronous reactance is 2 2/
ph. Determine the field excitation voltage E, when delivering rated MVA
at 0.90 power factor lagging.
Transcribed Image Text:Problem 4.4: A 3-phase, Y-connected synchronous generator is rated 15 MVA, 13.8 kV. Its resistance is negligible, and the synchronous reactance is 2 2/ ph. Determine the field excitation voltage E, when delivering rated MVA at 0.90 power factor lagging.
Expert Solution
steps

Step by step

Solved in 2 steps with 1 images

Blurred answer
Knowledge Booster
Load flow analysis
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning