Q.1: Non-metallic conduit must not be installed where extremes of ambient temperature, why?
Q: What precautions must be utilized and maintained when setting up or using a Delata 4 wire system…
A: A four-wire delta system is a three-phase delta connection with a centre-tap on one of the…
Q: What is the service entrance of a building electrical system and what are its components?
A: Service entrance of a building is related to house connections.
Q: 12. Which of the following statements about ground faults is true? A. They can happen if a…
A: Given Which of the following statements about ground faults is true? Mark the correct answer
Q: Take a look at the wire supplying your house, another residential house, commercial and industrial…
A: Wires selection is an important decision while designing the electrical connections for the…
Q: Explain the use of cable glanding
A: Cable glands are commonly defined as mechanical cable entry devices The use of cable glanding?
Q: Why is bonding of the conduit necessary when using reducing bushings to properly match a conduit to…
A: In such situations, conduit bonding is done to prevent or mitigate shock hazard as it provides a low…
Q: 17. In an air compressor system, the distribution piping can be bonded using the A. equipment…
A: Dear student as per our guidelines we are supposed to solve only one question.kindly repost other…
Q: 2. What fault occurs when Line and Neutral wires come with each other? Which device is actuated?
A: According to the given question, it is required to describe the fault which occurs when a line and a…
Q: What are the types of conduits?
A: There are different types of electrical conduits
Q: How can you calculate the maximum short-circuit current that can pass when the A-B ends of an outlet…
A: The detailed answer is solved below according to the given parameters and instructions in the…
Q: Discuss application and uses of earth leakage breaker ?
A: ELCB (Earth Leakage Circuit Breaker):- An ELCB (Earth Leakage Circuit Breaker) is an electrical…
Q: Define cable rating in a built environment
A: Cable selection and application : It is essential to know cable construction, characteristics,…
Q: What type of conduit that should be used where corrosion is a factor?
A:
Q: a system or circuit conductor (one that carries current), that is intentially grounded is referred…
A: The grounding is done to provide path for excess flow of current in order to prevent the devices or…
Q: 4. What is the effect of laid cables in proximity to each other?
A: The effect of laid cables in proximity also called as proximity effect which means the interaction…
Q: Which of the following is not a criteria for the mechanical design of an overhead line? O Minimum…
A: over head lines are designed based on distance between conductor and earth , tensile stress ,…
Q: 1. What is the proper size copper grounding electrode conductor for a 100-ampere service that…
A: Given-Rating of service conductor=100 ASize of phase conductor= 3/0 AWG
Q: 1. Identify and describe the step-by-step process used to pull cable and also describe the…
A: The step-by-step process used to pull cable STEP 1: Check the Cable Width and Pipeline to make sure…
Q: QI/B: For underground cables, what is the purpose of using insulation part?
A: Given : In the question they want to know the purpose of the insulation part of the cables which…
Q: How can you calculate the maximum short-circuit current that can pass when the A-B ends of an outlet…
A: The detailed answer is solved below according to the given parameters and instructions in the…
Q: A- Discuss the following claimed arguments: 1- Guard rings are recommended in low voltage as…
A: 1) Guard ring Figure shows electrical equivalent circuit of insulator discs connected at tower.…
Q: 4. Why are the outer metal parts of electrical appliances grounded?
A:
Q: wire size no.12 awg
A: AWG or American Wire Gauge is the US standard measure for the diameter of electrical conductors AWG…
Q: This discussion relates to Bonding. Whys is bonding of the conduit necessary when using reducing…
A: Bonding becomes necessary to reduce the risk of shock and it also provides a low impedance path to…
Q: 45. What section of the Code prohibits the use of sheet metal screws as a means of attaching…
A: As per the bartleby policy you can ask one question at a time so please ask other questions a…
Q: 1. With the help of suitable example differentiate between Open and Closed-loop systems?
A: As per our company guidelines we are supposed to answer only first one question. According to the…
Q: How would you draw the root locus for this system?
A: Control system is defined through the transfer function. The control system has to be stable for…
Q: What is the type,application and rating of cables?
A: Types of cable are classified according to their Voltage level .
Q: 4.Justify: why electrical isolation and theft prevention are the advantages of non-conductive cable?
A: According to the given question, it is required to determine the reason why non-conductive cables…
Q: 14. During normal operation of a typical 120-volt appliance circuit, current flows through the hot,…
A: Given: A 120 volt appliance and during its normal operation the flow of current is through hot,…
Q: What is the meaning of "system redundancy" in aircraft electrical systems? Explain why system…
A: We have given the following problem What is the meaning of "system redundancy" in aircraft…
Q: Justify: why electrical isolation and theft prevention are the advantages of non-conductive cable?
A: The main advantages of non conductive cable is it's isolation from the rest and most of the…
Q: What is the name and purpose of the following components of the Arduino board:
A: 1. Digital Pins There are 13 digital pins available in the Arduino. These pins will act like input…
Q: 17. Which of the following can be used to bond the metal parts at services? A. Ground clamps B.…
A: 18. Neutral disconnector link is used to disconnect the neutral from terminals where the neutral is…
Q: What do you mean by permissible current loading of an underground cable?
A: Permissible current loading: It is the maximum amount of current the cable can carry without any…
Q: What is grading of cables, explain.
A: Grading is defined as the process of equalizing the stress in the dielectric of the cable.…
Q: What is grading of cables.Explain?
A: In case of underground cable insulating layer very close to the conductor experiences maximum…
Q: what is the voltage between neutral and protective earth conductor in the TN-S earthing schemes…
A: In TN-S earthing scheme, T stands for solid earthing, N denotes the presence of the conductor having…
Q: Explain the relevance of earthing and bonding in an electrical Installation.
A: Earthing is used to protect us from an electric shock. It is done by providing a path (a protective…
Q: Is it okay to use a cable tray for the horizontal path of telephone lines to their specific outlets?…
A: EMT conduit size (inch) Number of cable 1 4 1-1/4 6 1-1/2 8 2 14 2-1/2 17
Q: The wording that I am running into with questions such as "The number of conductors required to be…
A: The number of conductors required to be installed between three-way and four-way switches is white…
Q: Describe the various methods of laying underground cables. What are the relative advantages and…
A: Proper laying and attachment of fittings decide the reliability of underground cables. The fittings…
Q: What is the smallest size conduit that can fit 13 #8 RWU90 conductors?
A: Given: 13 #8 RWU90 conductors The diameter of one cable of the #8 RWU90 conductor is 0.306 inches.…
I want FULL answer ASAP
Step by step
Solved in 2 steps
- The arrangement of grounding connections shall ensure that the disconnection or the removal of a luminaire, receptacle, or other device fed from the box does not interrupt the electrical continuity of the ____________ providing an effective ground-fault current path. grounding conductor(s) ungrounded conductor(s) equipment grounding conductor(s) all of these.If multiple grounding connection result in objectionable current, which of the following alteration can be permitted so long as the effective ground-fault current path isn't interrupted ? A. Taking remedial action approved by the authority having jurisdiction. B. Disconnecting all the grounding connection. C. Maintaining the location of the grounding connection. D. Interrupting the continuity of all conductive paths2. When working on a high - voltage system , it is best to keep anyone who is not part of the ser vice away from you and the car by creating a buffer zone around the car . Technician A makes sure the outside edges of the zone are at least one foot away from the car . Technician B places B orange cones to define the outer boundaries of the zone. Who is correct ?
- For residential wiring, not less than one 15-ampere lighting branch circuit should be provided for every ____________ ft2 of floor area. If 20-ampere lighting branch circuits are used, provide one 20-ampere lighting branch circuit for every ____________ ft2 of floor area21.Which of the following wiring methods may be used inside the duct used for vapor removal and ventilation of commercial type cooking equipment? (a.) nonmetallic sheathed cable (b.) EMT (c.) rigid steel conduit (d.) none of these 22. Ground-fault circuit-interrupter (GFCI) protection is required in all of the following locations EXCEPT: (a.) kitchen receptacles in an office building lunchroom installed within 6’ of the sink (b.) kitchen receptacles in a dwelling installed to serve counter top surfaces 10’ away from the sink (c.) receptacles in an office building restroom which has only a basin and toilet (d.) receptacle provided for servicing a rooftop air conditioning unit on the roof of a warehouse 23. Where GFCI protection is located in the power supply cord for an outdoor portable sign, the ground-fault circuit interrupter shall be located within _____inches of the attachment plug. (a.) 6 (c.) 18 (b.) 12 (d.) 24a. Is it permissible to install low-voltage Class 2 systems in the same raceway or enclosure with light and proper wiring? ______ b. Which Code section covers this? ______
- True or False: A heating and air-conditioning service technician can usually troubleshoot heating and air-conditioning systems without the voltage being supplied to the equipment.Are double locknuts an acceptable bonding method for Class 1, Division 1 Hazardous locations? If not, list an acceptable method, backing up your answer with a code citation.18. Which of the following would help avoid the choke effect in grounding electrode conductors?A. Installing a main bonding jumperB. Using an approved polyvinyl chloride conduitC. Applying solder to the connectionD. Using bonding bushes on the ends of the raceway
- 14. The amount of fault current that bonding connections have to endure is related to which of thefollowing?A. The quality of the fittings that were chosen for the systemB. The amount of available fault current delivered by the system or utilityC. The type of equipment and the location in the systemD. The number of connections that are part of the listed assembly13.B. The amount of fault current that bonding connections have to endure is related to which of thefollowing?A. The quality of the fittings that were chosen for the systemB. The amount of available fault current delivered by the system or utilityC. The type of equipment and the location in the systemD. The number of connections that are part of the listed assembly13.C. What is the most common grounding electrode used to connect utility service equipment to Earth?A. Ground rodB. PipeC. PlateD. Ground ringQUESTION 9 When a ground wire is connected to an interior gas piping system and the underground portion of the gas pipe into the building is plastic, which of the following is (or are) true? a A.This would be approved by code as the gas pipe is only being bonded to the electrical system. b B.This installation would be approved by code, as the gas pipe is not a grounding electrode. c C.Both A and B d D.Neither A nor B