the answer is 37.65microF pls provide the solution of the given problem.

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter2: Fundamentals
Section: Chapter Questions
Problem 2.14P: A single-phase source is applied to a two-terminal, passive circuit with equivalent impedance...
icon
Related questions
Question
100%

the answer is 37.65microF

pls provide the solution of the given problem.

4. A three phase, 50HZ, industrial load with a total rating of 25.5KW, 0.85 pf lagging will improve its performance
by the method of power factor correction via condenser equipment to 0.92 lagging. Calculate the condenser rating
per phase in microfarads required by this system if it energized at the supply entrance with a per phase voltage
219.3868 V.
Transcribed Image Text:4. A three phase, 50HZ, industrial load with a total rating of 25.5KW, 0.85 pf lagging will improve its performance by the method of power factor correction via condenser equipment to 0.92 lagging. Calculate the condenser rating per phase in microfarads required by this system if it energized at the supply entrance with a per phase voltage 219.3868 V.
Expert Solution
steps

Step by step

Solved in 2 steps with 1 images

Blurred answer
Knowledge Booster
Nodal analysis
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning