The load current at Z of a two wire distributor XYZ is 30 A at 0.707 lagging power factor. The load current at Y is 20 A at 0.8 lagging power factor. Both power factors are referenced to their load voltage. If the voltage at Z is to be 230 V, find the value of the voltage to be maintained at X. The loop impedance of section XY is 0.1 + j 0.3 Ω and the loop impedance of section YZ is 0.08 + j 0.24 Ω.

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter2: Fundamentals
Section: Chapter Questions
Problem 2.48P
icon
Related questions
icon
Concept explainers
Question

The load current at Z of a two wire distributor XYZ is 30 A at 0.707 lagging power factor. The load current at Y is 20 A at 0.8 lagging power factor. Both power factors are referenced to their load voltage. If the voltage at Z is to be 230 V, find the value of the voltage to be maintained at X. The loop impedance of section XY is 0.1 + j 0.3 Ω and the loop impedance of section YZ is 0.08 + j 0.24 Ω.

Expert Solution
steps

Step by step

Solved in 2 steps with 2 images

Blurred answer
Knowledge Booster
Types of Distribution in Power System
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning