The terminal voltage of a 3-φ generator is 19053 V, line-to-line. The load draws a current of 1515 A, leading, with a phase angle of 30o. The total real power, drawn by the load would be:

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter2: Fundamentals
Section: Chapter Questions
Problem 2.16MCQ: With generator conyention, where the current leaves the positive terminal of the circuit element, if...
icon
Related questions
Question

The terminal voltage of a 3-φ generator is 19053 V, line-to-line. The load draws a current of 1515 A, leading, with a phase angle of 30o. The total real power, drawn by the load would be: 