Two 6600/440 Volts transformers, A is 250 kVA and B is 500 kVA, have the following impedance/phase: Ra = 0.008 ohms, Xa = 0.035 ohms, Rb = 0.003 ohms, Xb = 0.019 ohms How will they share a load of 600 kVA at a power factor of 0.8 lagging if the load voltage is 440 V? The kVA and p.f. of each transformer are required.
Two 6600/440 Volts transformers, A is 250 kVA and B is 500 kVA, have the following impedance/phase: Ra = 0.008 ohms, Xa = 0.035 ohms, Rb = 0.003 ohms, Xb = 0.019 ohms How will they share a load of 600 kVA at a power factor of 0.8 lagging if the load voltage is 440 V? The kVA and p.f. of each transformer are required.
Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter3: Power Transformers
Section: Chapter Questions
Problem 3.43P: Three single-phase transformers, each rated 10MVA,66.4/12.5kV,60Hz, with an equivalent series...
Related questions
Question
Two 6600/440 Volts transformers, A is 250 kVA and B is 500 kVA, have the following impedance/phase:
Ra = 0.008 ohms, Xa = 0.035 ohms, Rb = 0.003 ohms, Xb = 0.019 ohms
How will they share a load of 600 kVA at a power factor of 0.8 lagging if the load voltage is 440 V? The kVA and p.f. of each transformer are required.
Expert Solution
This question has been solved!
Explore an expertly crafted, step-by-step solution for a thorough understanding of key concepts.
This is a popular solution!
Trending now
This is a popular solution!
Step by step
Solved in 2 steps with 2 images
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning