W(e,fan1) =40 kW and is operated for 5,800 hours/year, and (b) the supply fan 2 is rated at kW(e,fan2) =38 kW and is operated for 6,100 hours/year, and (c) the VFD operates according to the following load profile: % of Speed Fan 1, hours Fan2, hours 100 350 480 90 485 750 80 1080 980 70 1350
W(e,fan1) =40 kW and is operated for 5,800 hours/year, and (b) the supply fan 2 is rated at kW(e,fan2) =38 kW and is operated for 6,100 hours/year, and (c) the VFD operates according to the following load profile: % of Speed Fan 1, hours Fan2, hours 100 350 480 90 485 750 80 1080 980 70 1350
Electricity for Refrigeration, Heating, and Air Conditioning (MindTap Course List)
10th Edition
ISBN:9781337399128
Author:Russell E. Smith
Publisher:Russell E. Smith
Chapter13: Heating Control Devices
Section: Chapter Questions
Problem 1RQ
Related questions
Question
An energy service company agreed to convert all 18 constant volume air-handling units (AHUs) within a commercial building into variable-air-volume systems by installing variable frequency drives (VFDs) and VAV terminal boxes. To verify fan energy savings, it was agreed to meter only two AHU. Metering all 18 AHUs was determined to be economically infeasible.
The metering of AHUs revealed the following:
(a) the supply fan 1 is rated at kW(e,fan1) =40 kW and is operated for 5,800 hours/year, and
(b) the supply fan 2 is rated at kW(e,fan2) =38 kW and is operated for 6,100 hours/year, and
(c) the VFD operates according to the following load profile:
% of Speed Fan 1, hours Fan2, hours
100
350
480
90
485
750
80
1080
980
70
1350
1240
60
1940
2010
50
210
320
40
265
210
30
120
110
It was agreed that the energy use of one motor is proportional to its speed squared. Determine the fan energy and cost savings for the CV to VAV conversion for all the AHUs as stipulated in the agreement which states that the annual fan energy savings for all the AHUs is simply 18 times the average fan energy savings estimated from the metered AHUs. Assume that electricity costs $0.11/kWh.
Question 10 options:
the annual fan energy saving is 4092.8 MWh/yr and cost saving is $450206/yr
the annual fan energy saving is 3592.8 MWh/yr and cost saving is $390206/yr
the annual fan energy saving is 3892.8 MWh/yr and cost saving is $420206/yr
the annual fan energy saving is 3792.8 MWh/yr and cost saving is $410206/yr
Expert Solution
This question has been solved!
Explore an expertly crafted, step-by-step solution for a thorough understanding of key concepts.
Step by step
Solved in 3 steps
Knowledge Booster
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.Recommended textbooks for you
Electricity for Refrigeration, Heating, and Air C…
Mechanical Engineering
ISBN:
9781337399128
Author:
Russell E. Smith
Publisher:
Cengage Learning
Electricity for Refrigeration, Heating, and Air C…
Mechanical Engineering
ISBN:
9781337399128
Author:
Russell E. Smith
Publisher:
Cengage Learning