18.) A load of 35 kVA, with .65 power factor lagging is connected to a 230 volts line. How much capacitive reactive power is needed to correct the power factor to 0.78 lagging? Express in four decimal places. Your answer

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter2: Fundamentals
Section: Chapter Questions
Problem 2.10P: For the circuit element of Problem 2.3, calculate (a) the instantaneous power absorbed, (b) the real...
icon
Related questions
Question
18.) A load of 35 kVA, with .65
power factor lagging is
connected to a 230 volts line.
How much capacitive reactive
power is needed to correct
the power factor to 0.78
lagging? Express in four
decimal places.
Your answer
Transcribed Image Text:18.) A load of 35 kVA, with .65 power factor lagging is connected to a 230 volts line. How much capacitive reactive power is needed to correct the power factor to 0.78 lagging? Express in four decimal places. Your answer
Expert Solution
steps

Step by step

Solved in 4 steps with 4 images

Blurred answer
Knowledge Booster
Lag, Lead and Lead-Lag Compensator
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning