5. A 150 kVA transformer has iron-loss of 1-4 kW and full-load copper loss of 2-8 kW. Calculate (1) the efficiency of transformer at full-load (ii) the maximum efficiency of the transformer and (iii) the output power at the maximum level of efficiency. Assume unity power factor. [(1) 97-2 % (ii) 98-13 % (iii) 106-05 kW]
5. A 150 kVA transformer has iron-loss of 1-4 kW and full-load copper loss of 2-8 kW. Calculate (1) the efficiency of transformer at full-load (ii) the maximum efficiency of the transformer and (iii) the output power at the maximum level of efficiency. Assume unity power factor. [(1) 97-2 % (ii) 98-13 % (iii) 106-05 kW]
Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter3: Power Transformers
Section: Chapter Questions
Problem 3.57P: A two-winding single-phase transformer rated 60kVA,240/1200V,60Hz, has an efficiency of 0.96 when...
Related questions
Question
I need the answer as soon as possible
Expert Solution
This question has been solved!
Explore an expertly crafted, step-by-step solution for a thorough understanding of key concepts.
This is a popular solution!
Trending now
This is a popular solution!
Step by step
Solved in 3 steps
Knowledge Booster
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning