50MVA 22/220KV X=10% SOMVA 220/11kV X-5% T1 T2 Line 1 65MVA 15kV 220kV X-15.5 M T3 T4 100MVA Line 2 Load 22kV 110kV 45MVA X-15% 10kV SOMVA SOMVA 22/110kV pf = 0.5 lagging 110/11kV X-10% X-5% Figure Q2(b)
Q: QUESTION 3: Refer to the following figure. The circuit parameters are: V*= 4.5 V, V = -4.5 V and R1…
A: The transistor is a three-terminal device used for the regulation of signals. It is used for…
Q: What is the phase angle? R14 kn G+ :0.04 µF L14 H 497 V 750 Hz O A. 61.4° B. 28.5° O C.-28.5° O D.…
A:
Q: The switch in Figure Q2(c) has been in position a for a long time. At t = 0 s, the switch moves to…
A:
Q: If module with 60 cell measures Voc = 39.3V. What is the open circuit voltage for a module with 72…
A:
Q: 10 2 cos 10r V (+ 1F |1 H
A:
Q: (d) Sketch the spectrum of the sampled signal xs(t) when: = 1.5 Nyquist rate = 0.25 Nyquist rate а.…
A: Given the signal as shown below: x(t)=sinc2tπ d) We need to sketch the spectrum of the sampled…
Q: QUESTION 6 A PIN produces an average photocurrent of 1 mA, when exposed to a constant flow of…
A: Given information about a PIN is, Photocurrent is Ip=1 mA=1×10-3 A. Bandwidth is B=100 MHz=100×106…
Q: Design a counter to produce the following sequence. Use J-K flip-flops. 0, 2, 1, 3, 0, .
A:
Q: The scale of moving iron instrument is linear.
A: Moving Iron Instrument:
Q: Q3: Find the h-parameters for the two-port network shown in Figure 2. ,30 0.5 V, 412 V, 31
A:
Q: ransient is R 1=0 ww ell V, O Under damped O Critically damped O Over damped
A: In this question we will find system type for series RLC circuit using given data... Note :- as per…
Q: (а) АВ + АB + АBС (b) АВ(С + D) (с) (А + В)(В + А)
A:
Q: (d) Sketch the spectrum of the sampled signal xs(t) when: a. fs = 1.5 Nyquist rate b. fs %3D = 0.25…
A: Given the signal as shown below: x(t)=sinc2tπ d) We need to sketch the spectrum of the sampled…
Q: Calculate a series RC value that will produce a V = 7.59 V output at f = 87 Hz when V 20 V at f = 87…
A:
Q: Given the following circuit and Vc(0-) = -2V and iL(0-) = 2 mA, find iL(t) for t >0 sec 1H + 2 k2…
A: Brief description: In the given question they have mentioned a second order circuit which consists…
Q: 1 A coil of resistance 5ohms and inductance 120mH is in series with a 100UF capacitor, is connected…
A:
Q: FIND THE LAPLACE TRANSFORM OF -4t te*+ smat sinst
A: We need to find out Laplace transform of given signal.
Q: 3. For the circuit shown in Fig. 3.20, determine the load impedance Z for maximum power transfer (to…
A:
Q: Create a CE circuit with a voltage gain of 5 and a 500 ohm output impedance. Assume RE has a 300 mV…
A:
Q: Assuming ideal diode the voltage across the resistor R2 in the circuit shown in the Figure is: R1 E1…
A:
Q: d² x + 2 dt 2 * + 5x = e-t sin t; dx x(0) = 0 x'(0) = dt2
A:
Q: Find IL whing Souvce tranlyrimation
A:
Q: Calculate a series RC value that will produce a V = 7.59 V output at f = 87 Hz when V = 20 V at f =…
A:
Q: A Y-connected balanced 3 phase source with z=0.2+j0.1/phase is connected to a Y-connected balanced…
A: The solution is given below
Q: Solve for phase and line current of the given balanced three phase system with the ff loads: Vab=…
A: In this question, We need to Solve for phase and line current of the given balanced three phase…
Q: If module with 60 cell measures Voc = 39.3V. What is the open circuit voltage for a module with 72…
A:
Q: For the following message signal: f(t) = 7 cos w, t + 2 cos 5w, t, consider the output SNR for the…
A: FM refers to frequency modulation, where the information is transferred by changing the frequency of…
Q: Assuming ideal diode the voltage across the resistor R2 in the circuit shown in the Figure is: R1 E1…
A:
Q: QUESTION 13: Design a MOSFET current source with the configuration shown in the following figure.…
A: Given,The MOSFET parameters are,V+=2.5 VV- = 0VVTN=0.4 Vk'n = 88 μA/V2λ=0andIREF=235 μAIo=55…
Q: 20 V 2.2 k2 470 k2 1 k2 5 uF he = 140 h = 0.86 kQ h= 1.5 x 10 4 ho 25 uS 5 µF + %3D 1.2 k2 10 µF
A:
Q: In Figure Q2 (b), given that the voltage source, V, is a step function. The current flow through the…
A:
Q: A 280cm coil is carrying 10A current along the negative z-axis (downward direction). The coil is…
A: We need to find force on current carrying wire .
Q: If module with 60 cell measures Voc = 39.3V. What is the open circuit voltage for a module with 72…
A:
Q: Develop a circuit that will provide an output voltage that is -4 Vm if the input voltage is Vmsinwt
A: To obtain the -Vm at the output, we need to design a voltage quadrupler. The circuit of the voltage…
Q: Assuming ideal diode the voltage across the resistor R2 in the circuit shown in the Figure is: R1 E1…
A:
Q: esign a self-bias network using a JFET transistor with IDSS=8 in mA and VP=-5V to have a Q-point at…
A:
Q: A circuit containing capacitors and inductors is shown in Figure Q1(a). Find the current I3. C =20µF…
A:
Q: Point charges 120 nC, -44 nC, and 83 nC are located at (-1,0, 2), (0, 0, 0), and (1, 5, –1),…
A: Since cube side is 6cm and center is at origin so both side distance from center will 3 cm Look into…
Q: For the bridge rectifier circuit shown in the Figure, assuming practical diodes, the peak value of…
A:
Q: Compute for the percent modulation of the figure below.
A:
Q: T: Find the transfer function of the high pass filter shown in Fig1.
A:
Q: 5. A welder machine operates automatically as follows : 30A current in 10 seconds, 20A in 10 sec.,…
A:
Q: In an undisturbed airstream inside a wind tunnel, the pressure is 101325 Pa, density is 1.225 kg/m^3…
A:
Q: b) The z-transform of x[n]is X(z)= Z>5. Solve the z-transform of the (z+0.5) following using…
A: Since you have asked multiple questions in a single request, we will be answering only the 1st…
Q: Q T: Find the transfer function of the high pass filter shown in Figl. C R1 + O Vi R3 R2 Vo
A:
Q: QUESTION 2: Consider an ideal inverting op-amp in Figure P9.14. Given R1 = 5 kN, R2 = 10.7 kN, and…
A:
Q: 'shows the block diagram representation of a control system. Simplify the following block diagram…
A:
Q: OPAMP"Amplifiers 2-Numerical five different applications for OPAMP
A: Operation amplifier: It is a device which a can be used for both AC & DC signal amplication and…
Q: he transistor circuit with beta as 10o. Answer the following items below. Ok Ohrh 16 V 2.7 k Ohm
A:
Q: A superheterodyne receiver is to tune the range 88.IMHZ to 107.1MH2. The RF circuit inductance is…
A:
Step by step
Solved in 4 steps with 3 images
- Consider the single-line diagram of the power system shown in Figure 3.38. Equipment ratings are Generator 1: 1000MVA,18kV,X=0.2perunit Generator 2: 1000MVA,18kV,X=0.2p.u. Synchronous motor 3: 1500MVA,20kV,X=0.2p.u. Three-phase -Y transformers T1,T2,T3,T4,: 1000MVA,500kV,Y/20kV,X=0.1p.u. Three-phase YY transformer T5: 1500MVA,500kV,Y/20kVY,X=0.1p.u. Neglecting resistance, transformer phase shift, and magnetizing reactance, draw the equivalent reactance diagram. Use a base of 100 MA and 500 kV for the 50-ohm line. Determine the per-unit reactances.PowerWorid Simulator case Problem 3_60 duplicates Example 3.13 except that a resistance term of 0.06 per unit has been added to the transformer and 0.05 per unit to the transmission line. Since the system is no longer lossless, a field showing the real power losses has also been added to the oneline. With the LTC tap fixed at 1.05, plot the real power losses as the phase shift angle is varied from 10 to +10 degrees. What value of phase shift minimizes the system losses?Consider the oneline diagram shown in Figure 3.40. The three-phase transformer bank is made up of three identical single-phase transformers, each specified by X1=0.24 (on the low-voltage side), negligible resistance and magnetizing current, and turns ratio =N2/N1=10. The transformer bank is delivering 100 MW at 0.8 p.f. lagging to a substation bus whose voltage is 230 kV. (a) Determine the primary current magnitude, primary voltage (line-to-line) magnitude, and the three-phase complex power supplied by the generator. Choose the line-to-neutral voltage at the bus, Va as the reference Account for the phase shift, and assume positive-sequence operation. (b) Find the phase shift between the primary and secondary voltages.
- Consider the single-Line diagram of a power system shown in Figure 3.42 with equipment ratings given: Generator G1: 50MVA,13.2kV,x=0.15p.u. Generator G2: 20MVA,13.8kV,x=0.15p.u. Three-phase -Y transformer T1: 80MVA,13.2/165YkV,X=0.1p.u. Three-phase Y- transformer T2: 40MVA,165Y/13.8kV,X=0.1p.u. Load: 40MVA,0.8PFlagging,operatingat150kV Choose a base of 100 MVA for the system and 132-kV base in the transmission-line circuit. Let the load be modeled as a parallel combination of resistance and inductance. Neglect transformer phase shifts. Draw a per-phase equivalent circuit of the system showing all impedances in per unit.Consider three ideal single-phase transformers (with a voltage gain of ) put together as three-phase bank as shown in Figure 3.35. Assuming positive-sequence voltages for Va,Vb, and Vc find Va,Vb, and VC. in terms of Va,Vb, and Vc, respectively. (a) Would such relationships hold for the line voltages as well? (b) Looking into the current relationships, express IaIb and Ic in terms of IaIb and Ic respectively. (C) Let S and S be the per-phase complex power output and input. respectively. Find S in terms of S.Figure 3.39 shows a oneline diagram of a system in which the three-phase generator is rated 300 MVA, 20 kV with a subtransient reactance of 0.2 per unit and with its neutral grounded through a 0.4- reactor. The transmission line is 64km long with a cries reactance of 0.5-/km. The three-phase transformer T1 is rated 350MVA.230/20kV with a leakage reactance of 0.1 per unit. Transformer T2 is composed of three single-phase transformers, each rated 100 MVA, 127/13.2kV with a leakage reactance of 0.1 per unit. Two 13.2kV motors M1 and M2 with a subtransient reactance of 0.2 per unit for each motor represent the load. M1 has a rated input of 200 MVA with its neutral grounded through a 0.4- current-limiting reactor, M2 has a rated input of 100 MVA with its neutral not connected to ground. Neglect phase shifts associated with the transformers. Choose the generator rating as base in the generator circuit and draw the positive-sequence reactance diagram showing all reactances in per unit.
- Consider a three-phase generator rated 300MVA,23kV, supplying a system load of 240 MA and 0.9 power factor lagging at 230 kV through a 330MVA,23/230Y-kV step-up transformer with a leakage reactance of 0.11 per unit. (a) Neglecting the exciting current and choosing base values at the load of 100 MVL and 230 kV. Find the phasor currents IA,IB, and IC supplied to the load in per unit. (b) By choosing the load terminal voltage IA as reference, specify the proper base for the generator circuit and determine the generator voltage V as well as the phasor currents IA,IB, and IC, from the generator. (Note: Take into account the phase shift of the transformer.) (C) Find the generator terminal voltage in kV and the real power supplied by the generator in MW. (d) By omitting the transformer phase shift altogether, check to see whether you get the same magnitude of generator terminal voltage and real power delivered by the generator.The per-unit equivalent circuit of two transformers Ta and Tb connected in parallel, with the same nominal voltage ratio and the same reactan of 0.1 per unit on the same base, is shown in Figure 3.43. Transformer Tb has a voltage-magnitude step-up toward the load of 1.05 times that of Ta (that is, the tap on the secondary winding of Tb is set to 1.05). The load is represented by 0.8+j0.6 per unit at a voltage V2=1.0/0 per unit. Determine the complex power in per unit transmitted to the load through each transformer, comment on how the transformers share the real and reactive powers.Three single-phase two-winding transformers, each rated 25MVA,34.5/13.8kV, are connected to form a three-phase bank. Balanced positive-suence voltages are applied to the high-voltage terminals, and a balanced, resistive Y load connected to the low-voltage terminals absorbs 75 MW at 13.8 kV. If one of the single-phase transformers is removed (resulting in an open connection) and the balanced load is simultaneously reduced to 43.3 MW (57.7 of the original value), determine (a) the load voltages Va,Vb, and Vc; (b) load currents Ia,Ib, and Ic; and (c) the MVA supplied by each of the remaining two transformers. Are balanced voltages still applied to the load? Is the open transformer overloaded?
- Equipment ratings for the five-bus power system shown in Figure 7.15 are as follows: Generator G1:    50 MVA, 12kV, X=0.2 per unit Generator G2: 100 MVA, 15 kV, X=0.2 per unit Transformer T1: 50 MVA, 10 kV Y/138kVY,X=0.10 per unit Transformer T2: 100 MVA, 15 kV /138kVY,X=0.10 per unit Each 138-kV line: X1=40 A three-phase short circuit occurs at bus 5, where the prefault voltage is 15 kV. Prefault load current is neglected. (a) Draw the positive-sequence reactance diagram in unit on a 100-MVA, 15-kV base in the zone of generator G2. Determine (b) the Thévenin equivalent at the fault, (c) the subtransient fault current in per unit and in kA rms, and (d) contributions to the fault from generator G2 and from transformer T2.The following parameters are based on a preliminary line design: per unitVS=1.0, VR=0.9 per unit, =5000km,Zc=320,=36.8. A three-phase power of 700 MW is to be transmitted to a substation located 315 km from the source of power. (a) Determine a nominal voltage level for the three-phase transmission line, based on the practical line-loadability equation. (b) For the voltage level obtained in part (a), determine the theoretical maximum power that can be transferred by the line.For a balanced three-phase positive-sequence currents Ia,Ib,Ic, does the equation Ia+Ib+Ic=0 hold good?