A 2-wire d.c. distributor AB having 530 metres in length is fed from point A and is loaded as under: Distance from feeding point A (in metres) 150 340 420 530 Load (amperes) 20 40 40 50 The specific resistance of copper is 1·7 × 10−8 Ωm, Analyze the above Distribution scheme for the correct estimate of the cross-section of each wire in order that the voltage drop in the distributor shall not exceed 10 volts ?

EBK ELECTRICAL WIRING RESIDENTIAL
19th Edition
ISBN:9781337516549
Author:Simmons
Publisher:Simmons
Chapter6: Ground-fault Circuit Interrupters, Arc-fault Circuit Interrupters, Surge Protective Devices, Immersion Detection Circuit Interrupters, And Appliance Leakage Current Interrupters
Section: Chapter Questions
Problem 26R
icon
Related questions
Question

A 2-wire d.c. distributor AB having 530 metres in length is fed from point A and is loaded as under:

Distance from feeding point A (in metres)

150

340

420

530

Load (amperes)

20

40

40

50

 

The specific resistance of copper is 1·7 × 10−8 Ωm,

Analyze the above Distribution scheme for the correct estimate of the cross-section of each wire in order that the voltage drop in the distributor shall not exceed 10 volts ?

Expert Solution
steps

Step by step

Solved in 3 steps with 4 images

Blurred answer
Knowledge Booster
Photoelectric
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
EBK ELECTRICAL WIRING RESIDENTIAL
EBK ELECTRICAL WIRING RESIDENTIAL
Electrical Engineering
ISBN:
9781337516549
Author:
Simmons
Publisher:
CENGAGE LEARNING - CONSIGNMENT