A 24kVA, 6000/200 V transformer during the short circuit test the following result is obtained in the h.v. side: 200W, 4A, 100V. If the low voltage side is 200V at full-load and 0.8 flag what is the applied voltage at the high voltage side

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter3: Power Transformers
Section: Chapter Questions
Problem 3.57P: A two-winding single-phase transformer rated 60kVA,240/1200V,60Hz, has an efficiency of 0.96 when...
icon
Related questions
Question
A 24kVA, 6000/200 V transformer during the short circuit test the following result is
obtained in the h.v. side: 200W, 4A, 100V. If the low voltage side is 200V at full-load and 0.8
p.f.lag what is the applied voltage at the high voltage side
Transcribed Image Text:A 24kVA, 6000/200 V transformer during the short circuit test the following result is obtained in the h.v. side: 200W, 4A, 100V. If the low voltage side is 200V at full-load and 0.8 p.f.lag what is the applied voltage at the high voltage side
Expert Solution
steps

Step by step

Solved in 2 steps with 1 images

Blurred answer
Knowledge Booster
Single phase transformer
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning