A 3-phase star connected alternator is rated at 2000KVA 13.5KV. The armature effective resistance and synchronou reactance are 1.30 and 202, per phase respectively. Calculate the percent regulation at full-load for a power factor of a. 0.8 lagging b. 0.8 leading

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter12: Power System Controls
Section: Chapter Questions
Problem 12.13P
icon
Related questions
Question
A 3-phase star connected alternator is rated at 2000KVA 13.5KV. The armature effective resistance and synchronous
reactance are 1.30 and 202, per phase respectively. Calculate the percent regulation at full-load for a power factor of :
a. 0.8 lagging
b. 0.8 leading
Transcribed Image Text:A 3-phase star connected alternator is rated at 2000KVA 13.5KV. The armature effective resistance and synchronous reactance are 1.30 and 202, per phase respectively. Calculate the percent regulation at full-load for a power factor of : a. 0.8 lagging b. 0.8 leading
Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 2 steps with 2 images

Blurred answer
Knowledge Booster
Compensation Techniques in Transmission Line
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning