A 3Ø, Y-connected alternator is rated at 1,600KVA, 13.5KV. The armature effective AC resistance per phase is 1.52. The percentage regulation for a load of 1,280kW at unity power factor is 3.5%. Determine: (a) synchronous reactance of the alternator (b) %VR at full-load 0.8pf leading (c) What is the effect on %VR value if taken at half-load lagging pf? Justify and explain briefly your answer on one(1) sentence.

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter3: Power Transformers
Section: Chapter Questions
Problem 3.46P: The motors M1andM2 of Problem 3.45 have inputs of 120 and 60 MW, respectively, at 13.2 kV, and both...
icon
Related questions
Question

A 3Ø, Y-connected alternator is rated at 1,600KVA, 13.5KV. The armature effective AC resistance per phase is 1.5Ω. The percentage regulation for a load of 1,280kW at unity power factor is 3.5%. Determine:
(a) synchronous reactance of the alternator
(b) %VR at full-load 0.8pf leading
(c) What is the effect on %VR value if taken at half-load lagging pf? Justify and
explain briefly your answer on one(1) sentence.

A 3Ø, Y-connected alternator is rated at 1,600KVA, 13.5KV. The armature effective AC
resistance per phase is 1.52. The percentage regulation for a load of 1,280kW at unity
power factor is 3.5%. Determine:
(a) synchronous reactance of the alternator
(b) %VR at full-load 0.8pf leading
(c) What is the effect on %VR value if taken at half-load lagging pf? Justify and
explain briefly your answer on one(1) sentence.
Transcribed Image Text:A 3Ø, Y-connected alternator is rated at 1,600KVA, 13.5KV. The armature effective AC resistance per phase is 1.52. The percentage regulation for a load of 1,280kW at unity power factor is 3.5%. Determine: (a) synchronous reactance of the alternator (b) %VR at full-load 0.8pf leading (c) What is the effect on %VR value if taken at half-load lagging pf? Justify and explain briefly your answer on one(1) sentence.
Expert Solution
steps

Step by step

Solved in 2 steps with 2 images

Blurred answer
Knowledge Booster
Single phase transformer
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning