A 51 kVA load operates at 0.72 lagging power factor when connected to a 230 V, 60Hz AC source. The power factor is to be improved to 0.96 lagging. The power factor is to be corrected by a synchronous motor with 0.51 leading power factor, what is the kVA rating of the synchronous motor? The answer is 24.4643. Show solution pls

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter12: Power System Controls
Section: Chapter Questions
Problem 12.7P
icon
Related questions
Question

A 51 kVA load operates at 0.72 lagging power factor when connected to a 230 V, 60Hz AC source. The power factor is to be improved to 0.96 lagging. The power factor is to be corrected by a synchronous motor with 0.51 leading power factor, what is the kVA rating of the synchronous motor? The answer is 24.4643. Show solution pls 