A Carnot heat pump is used to maintain the temperature inside a building at 20 °C. Significantly, the colder it gets outside, the more heat is lost through the walls and windows of the building. Assume that 95 kW of heat are lost for each degree difference between the outside and the inside temperature. That means that the colder it gets, the harder the heat pump will need to work. However, for safety reasons, the controller circuit for the heat pump limits its electrical power consumption to 205 kW. What's the coldest it can get outside before the heat pump can't maintain the building temperature adequately?

Principles of Heat Transfer (Activate Learning with these NEW titles from Engineering!)
8th Edition
ISBN:9781305387102
Author:Kreith, Frank; Manglik, Raj M.
Publisher:Kreith, Frank; Manglik, Raj M.
Chapter5: Analysis Of Convection Heat Transfer
Section: Chapter Questions
Problem 5.12P
icon
Related questions
Question
Qout
W
H.P.
in
SOURCE
A Carnot heat pump is used to maintain the temperature inside a building at 20 °C.
Significantly, the colder it gets outside, the more heat is lost through the walls and
windows of the building. Assume that 95 kW of heat are lost for each degree difference
between the outside and the inside temperature. That means that the colder it gets, the
harder the heat pump will need to work. However, for safety reasons, the controller
circuit for the heat pump limits its electrical power consumption to 205 kW. What's the
coldest it can get outside before the heat pump can't maintain the building temperature
adequately?
°C
in
Transcribed Image Text:Qout W H.P. in SOURCE A Carnot heat pump is used to maintain the temperature inside a building at 20 °C. Significantly, the colder it gets outside, the more heat is lost through the walls and windows of the building. Assume that 95 kW of heat are lost for each degree difference between the outside and the inside temperature. That means that the colder it gets, the harder the heat pump will need to work. However, for safety reasons, the controller circuit for the heat pump limits its electrical power consumption to 205 kW. What's the coldest it can get outside before the heat pump can't maintain the building temperature adequately? °C in
Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 2 steps with 2 images

Blurred answer
Knowledge Booster
Convection
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, mechanical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Principles of Heat Transfer (Activate Learning wi…
Principles of Heat Transfer (Activate Learning wi…
Mechanical Engineering
ISBN:
9781305387102
Author:
Kreith, Frank; Manglik, Raj M.
Publisher:
Cengage Learning