Question

A three-phase two-winding transformer rated 1200 MVA, 14kV/162kV

has a leakage reactance of j0.10 pu. A three-phase load operating under

balanced positive phase sequence conditions on the secondary side

absorbs 1000 MVA at 0.9pf lagging with a terminal voltage of 161kV.

Use the given information to answer the following questions:

a) Draw a reactance diagram for the circuit.

b)Determine the voltage at the primary side of the transformer when

it is star connected.

c) Determine also the voltage at the primary when the primary side of

the transformer is delta connected.

Expert Solution
steps

Step by step

Solved in 4 steps with 4 images

Blurred answer
Knowledge Booster
Three Phase Transformer
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning