A generator is delivering power to infinite bus during post fault condition is 1.10 p.u at a power angle of 60 degrees. What is the maximum power that can be transferred? O a. 1.0 p.u O b. 1.1 p.u O c. 0.95 p.u O d. 1.27 p.u

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter11: Transient Stability
Section: Chapter Questions
Problem 11.4P
icon
Related questions
Question
A generator is delivering power to infinite bus during post fault condition is 1.10 p.u at
a power angle of 60 degrees. What is the maximum power that can be transferred?
O a. 1.0 p.u
O b. 1.1 p.u
O c. 0.95 p.u
O d. 1.27 p.u
Transcribed Image Text:A generator is delivering power to infinite bus during post fault condition is 1.10 p.u at a power angle of 60 degrees. What is the maximum power that can be transferred? O a. 1.0 p.u O b. 1.1 p.u O c. 0.95 p.u O d. 1.27 p.u