  1. A generator rated 600 KVA, 2,400 V, 60 Hz, 3 –phase, 6 poles and wye connected has 10% synchronous reactance. If a three – phase fault occurs, what will be the short circuit current?

(a). 1,443 A                   (b). 1,532 A

(c). 1,435 A                   (d). 1,426 A

A generator rated 600 KVA, 2,400 V, 60 Hz, 3 -phase, 6 poles and wye
connected has 10% synchronous reactance. If a three-phase fault occurs,
what will be the short circuit current?
(a). 1,443 A
(b). 1,532 A
(c). 1,435 A
(d). 1,426 A
Transcribed Image Text:A generator rated 600 KVA, 2,400 V, 60 Hz, 3 -phase, 6 poles and wye connected has 10% synchronous reactance. If a three-phase fault occurs, what will be the short circuit current? (a). 1,443 A (b). 1,532 A (c). 1,435 A (d). 1,426 A
Expert Solution
steps

Step by step

Solved in 2 steps with 2 images

Blurred answer
Knowledge Booster
Fault analysis
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning