A separately excited DC generator has rated terminal voltage and full load armature current of 200 V and 50 A respectively and rated speed of 1500 rpm. The generator armature resistance R, = 0.1 Q and field resistance of R; = 100n and field voltage of 150 V. Calculate: 1. The induced emf and torque at full load. 2. The emf, armature current and terminal voltage at rated speed when the field voltage is changed to 100V. 3. The developed torque at rated speed when the field voltage is changed to 120V.

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter11: Transient Stability
Section: Chapter Questions
Problem 11.3P
icon
Related questions
Question
A separately excited DC generator has rated terminal voltage and full load armature current of
200 V and 50 A respectively and rated speed of 1500 rpm. The generator armature resistance R,
= 0.1 0 and field resistance of R; = 100on and field voltage of 150 V.
Calculate:
1. The induced emf and torque at full load.
2. The emf, armature current and terminal voltage at rated speed when the field voltage is
changed to 100V.
3. The developed torque at rated speed when the field voltage is changed to 120V.
4. The emf, armature current and terminal voltage at half rated speed when the field
voltage is changed to 200V.
Transcribed Image Text:A separately excited DC generator has rated terminal voltage and full load armature current of 200 V and 50 A respectively and rated speed of 1500 rpm. The generator armature resistance R, = 0.1 0 and field resistance of R; = 100on and field voltage of 150 V. Calculate: 1. The induced emf and torque at full load. 2. The emf, armature current and terminal voltage at rated speed when the field voltage is changed to 100V. 3. The developed torque at rated speed when the field voltage is changed to 120V. 4. The emf, armature current and terminal voltage at half rated speed when the field voltage is changed to 200V.
Expert Solution
steps

Step by step

Solved in 5 steps

Blurred answer
Knowledge Booster
DC Generator
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning