A synchronous generator is rated 645 MVA, 24 kV, 0.9 pf iagging. It has a synchronous reactance 1.2 . The generator is feeding full load at 0.9 pf lagging at rated voltage. Calculate: (a) Excitation emf (E,) and power angle & (b) Reactive power drawn by the load Carry out calculations in pu form and convert the result to actual values.

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter11: Transient Stability
Section: Chapter Questions
Problem 11.8P
icon
Related questions
Question
A synchronous generator is rated 645 MVA, 24 kV, 0.9 pf lagging. It has a
synchronous reactance 1.2 . The generator is feeding full load at 0.9 pf
lagging at rated voltage. Calculate:
(a) Excitation emf (E,) and power angle &
(b) Reictive power drawn by the load
Carry out calculations in pu form and convert the result to actual values.
Transcribed Image Text:A synchronous generator is rated 645 MVA, 24 kV, 0.9 pf lagging. It has a synchronous reactance 1.2 . The generator is feeding full load at 0.9 pf lagging at rated voltage. Calculate: (a) Excitation emf (E,) and power angle & (b) Reictive power drawn by the load Carry out calculations in pu form and convert the result to actual values.
Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 3 steps with 3 images

Blurred answer
Knowledge Booster
Three Phase Transformer
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning