An 22kV, 100 MVA alternator is provided with differential protection. The percentage of winding be protected against phase to ground fault is 75%. The relay is set to operate when there is 20% out of balance current. Determine the value of the resistance to be placed in the neutral to ground connection.

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter10: System Protection
Section: Chapter Questions
Problem 10.27P
icon
Related questions
icon
Concept explainers
Question

An 22kV, 100 MVA alternator is provided with differential protection. The percentage of winding be protected against phase to ground fault is 75%. The relay is set to operate when there is 20% out of balance current. Determine the value of the resistance to be placed in the neutral to ground connection.