At a 115kV substation the PT raatio is 1000:1 and CT ratio is 1,200:5. The potential going into the wattmeter is 115V. What is the actual MW consumed when the wattmeter reads 736W hint: P=V*I
At a 115kV substation the PT raatio is 1000:1 and CT ratio is 1,200:5. The potential going into the wattmeter is 115V. What is the actual MW consumed when the wattmeter reads 736W hint: P=V*I
Chapter3: Determining The Required Number Of Branch Circuits, Lighting Outlets, And Receptacle Outlets
Section: Chapter Questions
Problem 6R: What is the unit load per square foot for dwelling units? See Table 220.12. __________
Related questions
Question
At a 115kV substation the PT raatio is 1000:1 and CT ratio is 1,200:5. The potential going into the wattmeter is 115V. What is the actual MW consumed when the wattmeter reads 736W hint: P=V*I
Use four decimal places for final answer if necessary.