CO2 12. A 1000 kVA, 3000V, 60 Hz, 3phase, Y-connected alternator has an CO3 armature effective resistance of 0.20 ohm. A field current of 40A CO4 produces a short circuit of 2O0A and an open circuit emf of 1040V between lines. Determine the full load percent regulation at 0.80 lagging power factor. A. 24.3% C. 26.5% B. 18.7% P. 13.5%

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter2: Fundamentals
Section: Chapter Questions
Problem 2.41P
icon
Related questions
Question

12

A 1000 kVA, 3000V, 60 Hz, 3phase, Y-connected alternator has an
armature effective resistance of 0.20 ohm. A field current of 40A
CO2
12.
CO3
CO4
produces a short circuit of 200A and an open circuit emf of 1040V
between lines. Determine the full load percent regulation at 0.80
lagging power factor.
A. 24.3%
C. 26.5%
B. 18.7%
D. 13.5%
Transcribed Image Text:A 1000 kVA, 3000V, 60 Hz, 3phase, Y-connected alternator has an armature effective resistance of 0.20 ohm. A field current of 40A CO2 12. CO3 CO4 produces a short circuit of 200A and an open circuit emf of 1040V between lines. Determine the full load percent regulation at 0.80 lagging power factor. A. 24.3% C. 26.5% B. 18.7% D. 13.5%
Expert Solution
steps

Step by step

Solved in 2 steps with 1 images

Blurred answer
Knowledge Booster
KVL and KCL
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning