Consider the system in which a generator is connected to an infinite bus through a double circuit transmission line as shown in Fig. 9.5. The per unit system reactances that are converted in a common base, are also shown in this figure. Let us assume that the infinite bus voltage is 1< 0°. The generator is delivering 1.0 per unit real power at a lagging power factor of 0.9839 to the infinite bus. While the generator is operating in steady state, a three-phase bolted short circuit occurs in the transmission line connecting buses 2 and 4 - very near to bus 4. The fault is cleared by opening the circuit breakers at the two ends of this line. We have to find the critical clearing time for various values of H. ELS j0.3 j0.1 j0.1 j0.2 j0.1 120°

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter12: Power System Controls
Section: Chapter Questions
Problem 12.9P
icon
Related questions
Question
Consider the system in which a generator is connected to an infinite bus through a double circuit
transmission line as shown in Fig. 9.5. The per unit system reactances that are converted in a common
base, are also shown in this figure. Let us assume that the infinite bus voltage is 1< 0°. The generator is
delivering 1.0 per unit real power at a lagging power factor of 0.9839 to the infinite bus. While the
generator is operating in steady state, a three-phase bolted short circuit occurs in the transmission line
connecting buses 2 and 4 - very near to bus 4. The fault is cleared by opening the circuit breakers at the
two ends of this line. We have to find the critical clearing time for various values of H.
T***
ELS 70.1
j0.3
j0.1
j0.2
j0.1
120°
Fig. 9.5 Schematic diagram of the power system of Example 9.4.
Transcribed Image Text:Consider the system in which a generator is connected to an infinite bus through a double circuit transmission line as shown in Fig. 9.5. The per unit system reactances that are converted in a common base, are also shown in this figure. Let us assume that the infinite bus voltage is 1< 0°. The generator is delivering 1.0 per unit real power at a lagging power factor of 0.9839 to the infinite bus. While the generator is operating in steady state, a three-phase bolted short circuit occurs in the transmission line connecting buses 2 and 4 - very near to bus 4. The fault is cleared by opening the circuit breakers at the two ends of this line. We have to find the critical clearing time for various values of H. T*** ELS 70.1 j0.3 j0.1 j0.2 j0.1 120° Fig. 9.5 Schematic diagram of the power system of Example 9.4.
Expert Solution
steps

Step by step

Solved in 2 steps with 4 images

Blurred answer
Knowledge Booster
Economic load dispatch
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning