determine the line-to-neutral (120 V)

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter3: Power Transformers
Section: Chapter Questions
Problem 3.64P: The per-unit equivalent circuit of two transformers Ta and Tb connected in parallel, with the same...
icon
Related questions
Question
Example 3.2
Using the transformer equivalent circuit found in Example 3.1, determine the line-to-neutral (120 V)
and line-to-line (240 V) fault currents in three-wire single-phase 120/240 V secondaries shown in
Figures 3.33 and 3.34, respectively. In the figures, R represents the resistance of service-drop cable
per conductor. Usually R is much larger than X for such cable and therefore X may be neglected.
Using the given dala, determine the following:
a. Find the symmetrical rms fault currents in the HV and LV circuits for a 120 V fault if R of the
service-drop cable is zero.
b. Find the symmetrical rms fault currents in the HV and LV circuits for a 240 V fault if R of the
service-drop cable is zero.
c. If the transformer is a CSPB type, find the minimum allowable interrupting capacity (in sym-
metrical rms amperes) for a circuit breaker connected to the transformer's LV terminals.
24.637 L 53.9 2
8.525 x 10 L 18.9 n
H
(x)
ISHV
120 V
7200 V
X2
120 V
x3
H2
8.525 x 10-3 L 18.9° 0
R> R
elehele
lelllllll
Transcribed Image Text:Example 3.2 Using the transformer equivalent circuit found in Example 3.1, determine the line-to-neutral (120 V) and line-to-line (240 V) fault currents in three-wire single-phase 120/240 V secondaries shown in Figures 3.33 and 3.34, respectively. In the figures, R represents the resistance of service-drop cable per conductor. Usually R is much larger than X for such cable and therefore X may be neglected. Using the given dala, determine the following: a. Find the symmetrical rms fault currents in the HV and LV circuits for a 120 V fault if R of the service-drop cable is zero. b. Find the symmetrical rms fault currents in the HV and LV circuits for a 240 V fault if R of the service-drop cable is zero. c. If the transformer is a CSPB type, find the minimum allowable interrupting capacity (in sym- metrical rms amperes) for a circuit breaker connected to the transformer's LV terminals. 24.637 L 53.9 2 8.525 x 10 L 18.9 n H (x) ISHV 120 V 7200 V X2 120 V x3 H2 8.525 x 10-3 L 18.9° 0 R> R elehele lelllllll
Expert Solution
steps

Step by step

Solved in 3 steps with 3 images

Blurred answer
Knowledge Booster
Analysis of Single Phase and Three Phase System
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning