Question

In all liquid refrigerant lines, the pressure at the bottom of a vertical rise is
greater than the pressure at the top of the rise. For R-134a, the pressure is
about 0.5144 lb/sq in or less for every vertical foot of pipe that is used. The
vertical rise between this condenser and evaporator is 7.5 feet. How much
less is the pressure at the top of the rise than at the bottom?

EVAPORATOR
7.5 ft
CONDENSER
Transcribed Image Text:EVAPORATOR 7.5 ft CONDENSER