fault location

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter9: Unsymmetrical Faults
Section: Chapter Questions
Problem 9.28P
icon
Related questions
icon
Concept explainers
Question
100%
4. Calculate three phase voltages and currents at fault location and
at Bus G for a phase-A to Ground (L-G) fault at bus H, for a system
as shown in Figure 2. Also draw the positive, negative, zero
sequence
networks
and their
interconnection diagram for this
particular fault.
90 MVA
90 MVA
132kV
H
132kV
Line section
Source
Source
B
100 MVA
100 MVA
132/69 kV
10%
132/69 kV
10%
Figure - 2
Transcribed Image Text:4. Calculate three phase voltages and currents at fault location and at Bus G for a phase-A to Ground (L-G) fault at bus H, for a system as shown in Figure 2. Also draw the positive, negative, zero sequence networks and their interconnection diagram for this particular fault. 90 MVA 90 MVA 132kV H 132kV Line section Source Source B 100 MVA 100 MVA 132/69 kV 10% 132/69 kV 10% Figure - 2
Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 2 steps with 3 images

Blurred answer
Knowledge Booster
Fault analysis
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning