For the following single line diagram of a three-phase system, a three-phase fault occurs at point P and just before the fault the line voltage is 18 kV at P. Find out the transient fault current in pu and original value at point P. Take, the given kVA and kV of the G1 as the new base. [hint: the transient and sub-transient reactances of the synchronous generators are assumed to be same. But for the motors, assume that the transient one is 1.7 times of the sub-transient reactance.] 20,000 KV A 6.9KV 7000 KVA G1 5KV Tz 14% 11/33KV 33/6.9 AV 5+j8 2 G2 load 20000 KVA 15000 KVA 10% 12%0 25,000 KVA 6.9KV 8/% an srebtransien [AH tue mpedanees are given per- unit values)

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter7: Symmetrical Faults
Section: Chapter Questions
Problem 7.15P
icon
Related questions
Question
For the following single line diagram of a three-phase system, a three-phase fault occurs at
point P and just before the fault the line voltage is 18 kV at P. Find out the transient fault
current in pu and original value at point P. Take, the given kVA and kV of the G1 as the
new base.
[hint: the transient and sub-transient reactances of the synchronous generators are assumed
to be same. But for the motors, assume that the transient one is 1.7 times of the sub-transient
reactance.]
20,000 KV A
6.9KV
15%
G1
7000 KVA
5KV
Tz
14%
11/33KV
33/6.9 AV
5+j8 s2
(G2
load
20000 KVA
15000 KVA
10%
12%0
25,000 KVA
6.9KV
8%
as orebtsansient
[Au tue mpedanmees are given
per-unit values)
Transcribed Image Text:For the following single line diagram of a three-phase system, a three-phase fault occurs at point P and just before the fault the line voltage is 18 kV at P. Find out the transient fault current in pu and original value at point P. Take, the given kVA and kV of the G1 as the new base. [hint: the transient and sub-transient reactances of the synchronous generators are assumed to be same. But for the motors, assume that the transient one is 1.7 times of the sub-transient reactance.] 20,000 KV A 6.9KV 15% G1 7000 KVA 5KV Tz 14% 11/33KV 33/6.9 AV 5+j8 s2 (G2 load 20000 KVA 15000 KVA 10% 12%0 25,000 KVA 6.9KV 8% as orebtsansient [Au tue mpedanmees are given per-unit values)
Expert Solution
steps

Step by step

Solved in 4 steps with 2 images

Blurred answer
Knowledge Booster
Synchronous Generator
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning