line currents (IR, Ty and 1B). (c) Determine the total real supply power (W) for Q1(b) based on the 2 wattmeter measurements.
Q: In the experiment No.1, the power measurement using two wattmeter method for delta connected load,…
A: The solution is given below the statement is false.
Q: For an ac three-phase four wire system, having a voltage of 415 V, with load of 120 kW and…
A: Given three phase four wire systemHaving voltage V=415 vLoad P=120 kw Resistance R=0.05 ΩPower…
Q: The input power to a 3-phase star connected load is measured as 4.6KW. If the line voltage and line…
A: In this question we have given input power , voltage and current , we have to find out power…
Q: With proper figure, prove that two wattmeters are sufficient to calculate the power in a balanced…
A: With proper figure, prove that two wattmeters are sufficient to calculate the power in a balanced…
Q: a) Calculate the reading of each wattmeter in the circuit shown in Fig. below The value of Z, is…
A: Given Data:Z∅=40∠-30 ohmVBA=2403∠150 V
Q: Two wattmeters are connected into a 3-phase, 3-wire, 220V line indicate 3.5kW and 1.5kW. If the…
A:
Q: 1. Discuss the features of two-wattmeter method of power measurement. 2. What is the significance of…
A:
Q: With neat diagram, discuss the 3-phase power measurement using three wattmeter method and write down…
A: Three wattmeter method is used to measure the power in a 3-phase system. In this method, the power…
Q: 4. How far from a single-phase 240 volt source can you install #10 THW stranded copper conductors if…
A: It is given that: V=240 voltI=16 amp
Q: 2. Prove that the sum of the readings of the two wattmeter used to measure power in a 3 wire, Wye…
A:
Q: Q1: Calculate the total real power absorbed by the lond shown. if V416 V is applied, with and…
A: In the question, We are calculating the total real power and reading of watt-meters. 3 phase…
Q: substation is supplying 200 kVA and 150 kvar. Calculate the corresponding power and power factor.
A:
Q: Question 2: Consider the network shown in the following figure. Compute the magnitude of the line…
A: The solution can be achieved as follows.
Q: ) Find the ICA load current. b) Give the line voltage Vab. c) Calculate the total complex power…
A: In the circuit a) Find the ICA load current. b) Give the line voltage Vab. c) Calculate the total…
Q: The input power to a 3-phase star connected load is measured as 1.5KW. If the line voltage and line…
A: In a three phase system there are two ways to connect a three phase load. Star/Wye Connection Delta…
Q: The minimum number of wattmeter(s) required for measuring power of 3-phase balanced load is
A: Step1 In this question, we have to find out minimum number of wattmeters required for measuring…
Q: c) Cost of the Line a) Voltage level b) Nearness to load d) Cost of the centres substation 2. To…
A:
Q: In balanced 3-phase power measurement, the minimum number(s) of wattmeter required to measure the…
A: if system is n phase (n+1) wire then n watt meter is needed if system is n phase n wire then (n-1)…
Q: In two wattmeter 3-phase power measurement method, if the two wattmeter readings are equal then the…
A: Therefore, if the two wattmeter readings are equal then power factor of the circuit is unity (1).…
Q: In a 3-phase power measurement using two wattmeter method , if one wattmeter reads 2.5 times the…
A: We know formula of power factor angle for two watt method .
Q: Find out the sending end voltage (Vs) and %efficiency for the given readings VR(line to line)=…
A: Given VR(line to line)=382 vcosϕR=0.8IR=0.63 AResistance R=24 ΩXL=24 Ω
Q: In a 3-phase balanced star connected system, the least number of wattmeter essential to measure the…
A: in balanced system , total power = 3* power in single phase so total power in balanced three phase…
Q: A 3-phase transmission line operating at 10 kV has a resistance of 192. The percentage resistance of…
A: Given, A 3-phase transmission line with, Rated line voltage, V = 10 kV Resistance, R=1 Ω Base kVA =…
Q: n balanced star (wye) connected system, the line voltage is
A: THREE PHASE-BALANCED STAR OR WYE CONNECTION: 1. A central connecting point connecting one side of…
Q: Each phase of a delta-connected load comprises a resistor of 50Ω and a 50µF in series. Calculate (a)…
A: Please refer the attached images for the complete answer..
Q: VII. PROBLEMS : 1. How many wattmeters would be needed to measure the total three-phase power in a…
A: For measuring the power in three phase system the number of wattmeters required is always 1 less…
Q: In a balanced 220-volt 3-phase circuit, two wattmeters are connected to measure power. If the…
A: Given readings of two wattmeter, W1= 8.53 kWW2= -2.66 kW
Q: The input power to a 3-phase load i measured as 13kW. If the line voltag power factor of the load…
A:
Q: From the given circuit determine Line currents1,2, Total Current and Total Voltage. Provide…
A:
Q: In two wattmeter 3-phase power measurement method, if one wattmeter reads zero then the power factor…
A: FIND EXPLANATION BELOW
Q: In a 3-phase power measurement using two wattmeter method , if one wattmeter reads 2.5 times the…
A:
Q: Explain the use of three wattmeter method employed to measure power in a 3 phase, 4 wire system of…
A:
Q: In three phase power measurement using one watt-meter method, if the load is unbalanced then the…
A: Right Answer True
Q: In balanced and unbalanced 3-phase power measurement, the minimum number(s) of wattmeter required to…
A: The balanced star means the value of the current in all phases are same
Q: In the experiment No.1, the power measurement using two wattmeter method for star connected load,…
A:
Q: Q4: For the figure shown below a) Calculate the reading of each wattmeter in the circuit shown, when…
A: given Z=12 + j 46 load is delta connected
Q: 12:27 You 3/13/21, 11:27 AM 2. To transmit the power at 220kV over 3 phase 3 wire line, substation…
A: In this question , we have to tell that to transmit the power at 220 KV over 3 phase 3 wire line…
Q: 1. An 11kV,3 phase transmission line has a resistance of 1.5 ohms per phase and 12.73 milli henrys…
A:
Q: Q4: For the figure shown below a) Calculate the reading of each wattmeter in the circuit shown, when…
A: It is given that:
Q: 15. phase is 120 V and 100 A, respectively, calculate a) In a three-phase transmission power system,…
A:
Q: 3) Three similar coils, each having a resistance of 8 and an inductive reactance of 8 are connected…
A:
Q: Three identical coils, each having a resistance of 20Ω and a reactance of 20 Ω are connected in…
A: In Star Connection- Star connection phase voltage is line voltage divided by root 3. Line current…
Q: A 415 V, 3 phase, 4 wire system supplies power to three non-inductive loads. The loads are 25 kW…
A: The solution is given below
Q: 8kW is found by the two-wattmeter method to be the powerinput to a 3-phase motor. Determine the…
A: Given, P1+ P2= 8 kW .........(1)power factor= 0.85
Q: In the given power system network 220kV 11kV 11kV SkV a) What is the number of generating units? b)…
A: Two generating units T2 is tranformer
Q: Blondel's theorem is used to specify the number of wattmeters for power (c) measurement in a system…
A:
Q: a single line transmission line having 500 kva load at 2kv it resistance is 0.2 ohm and inductive…
A: Given data, A single transmission line having S=500 kVAVR=2 kVR=0.2 ΩXL=0.2 ΩPf cosϕR=0.707 leading…
Q: Question 5 Complete the sentence The power factor must be close to To insure that losses in the…
A: Given: Complete the sentence. The power factor must be close to ______ To ensure that losses in the…
Q: 1.7 A high-voltage direct-current (de) transmission line between Celilo, Oregon and Sylmar,…
A: Line voltage at Celilo, Oregon side V1=800 kV, Line current from Celilo, Oregon to Sylmar,…
Q: In the two wattmeter method of 3-phase power measurement, the access to the star point is not…
A:
Step by step
Solved in 3 steps with 3 images
- For the circuit element of Problem 2.3, calculate (a) the instantaneous power absorbed, (b) the real power (state whether it is delivered or absorbed). (c) the reactive power (state whether delivered or absorbed). (d) the power factor (state whether lagging or leading). [Note: By convention the power factor cos() is positive. If | | is greater than 90, then the reference direction for current may be reversed, resulting in a positive value of cos() ].With generator conyention, where the current leaves the positive terminal of the circuit element, if P is positive then positive real power is delivered. (a) False (b) TrueA short line having an impedance of (2 + j3) ohm interconnects two power stations A and B both operating at 11kV equal in magnitude and phase. To transfer 25 MW at 0.8 power factor lagging from A to B determine the voltage drop must be compensated by the booster so that the voltages are maintain the same at both ends.
- 1. A 69-kV, three-phase short transmission line is 16 km long. The line has a per phase series impedance of 0.125+j0.4375 Ω per km. Determine the sending end voltage, voltage regulation, the sending end power, and the transmission efficiency when the line delivers (a) 70 MVA, 0.8 lagging power factor at 64 kV. (b) 120 MW, unity power factor at 64 kV. Use lineperf program to verify your results. 2. A three-phase, 765-kV, 60-Hz transposed line is composed of four ACSR, l,431,000-cmil, 45/7 Bobolink conductors per phase with flat horizontal spacing of 14 m. The conductors have a diameter of 3.625 cm and a GMR of 1.439 cm. The bundle spacing is 45 cm. The line is 400 km long, and for the purpose of this problem, a lossless line is assumed. (a) Determine the transmission line surge impedance Zc, phase constant ß, Wavelength, the surge impedance loading SIL, and the ABCD constant. b) The line delivers 2000 MVA at 0.8 lagging power factor at 735 kV. Determine the sending end quantities and…An AC three phase distribution system (given in Figure 2), which has end user with balanced three phase (10A) load, is given in the figure. The phase-neutral voltages of the transformers are given as V1=224V, V2=225V, V3=228V and V4=231V respectively. a) Calculate phase-neutral voltage of the bus-bar (B). b) Calculate currents of the transformers (I1, I2, I3 and I4) c) Calculate phase-neutral voltage of the point K while the output of TR3 and TR4 (xy) have been short circuited for a transient time (transformers are still operational) by the line fault.Non-Reactive Loads of 10kW, 20kW and 12kW are connected between the neutral and the red, yellow and blue phases respectively of 3-phase, 4 wire . The line voltage is 400. If a three phase motor is now started ,taking 150 A from the lines at a power factor of 0.3 lagging What should be the total current in each line and the neutral wire? Find the total real and reactive power supplied to the loads
- Refer to the 5-bus data given below. Sbase = 400 MVA, the base voltage is 15.0 kV for buses 1 and 3, and 345 kV for buses 2, 4, 5. Note that 1-5 and 3-4 are 15/345 kV transformers.a) Draw a one-line diagram of the power system.b) Find the elements Y23, Y43, Y11 Y33 of the system bus admittance matrix.Consider the following power system model with the following entities:i. A generator generates a sinusoidal waveform with amplitude of 300 V and angular frequency of 5 radians,ii. The transmission line has a resistance of 1Ω, andiii. A capacitive load with a value of 2F presents at the end of the system. Answer the following questions:(a) Draw the relevant diagram and label all entity values of the power system as described above.(b) Replacing the real source in Figure from part (a) with a complex source, find the response of the steady-state capacitor voltage in time-domain.(d) Repeat the sub-question (a) above, now showing calculations in s-domain.An Alternator having three-phase, 3-wire ABC system supplying an effective line voltage of 120 V, has an a three-impedances of 50 / 45 ohms in Delta connection. Assume that Vbc is the reference vector. In problem above, assuming that it is Wye connected load and VAN is the reference vector. Determine the total true power, reactive power, apparent power of the connected load. What is the capacity in Kva of synchronous generator if the connected load is 85%
- A single phase transmission line is delivering 490 kVA load at 14 kV. Its resistance is 6 Ω and inductive reactance is 7 Ω if the load power factor is 0.7 lagging. Determine the: A) Current through the line. B) Sending end voltage. C) Sending end power factor. D) Regulation of transmission line. E) Efficiency of transmission line.single circuit three-phase line, 60 Hz, 18 km has a total resistance and inductive reactance of 4.242 ohm and7.451 ohm per phase respectively. The line delivers 2500 kW to a balanced load at 11 kV. (1) determine the sending-end voltage when the power factor is (i) 80% lagging, (i) unity, and (ii) 90 % leading, (2) draw the phasor diagrams of the line at the above (3) determine the voltage regulation of the line at the above power factors.Two balanced Y-connected loads in parallel, one drawing 15 kW at 0.6 power factor lagging andthe other drawing 10 kVA at 0.8 power factor leading, are supplied by a balanced, three-phase,480-volt source.a. Draw the power triangle for each load and for the combined load.b. Determine the power factor of the combined load and state whether lagging or leading.c. Determine the magnitude of the line current from the source.