Problem 1 – The 4.16kV distribution station capacitor bank below consists of 3 ungrounded double-wye (UGDY) stages with a main breaker connecting Stage 1 capacitors directly and with Stages 2 and 3 through vacuum switches.   Capacitor Unit Ratings: 2.400kV, 200kVAR CT Data: Main Breaker:  1500/5, Neutral CT:  50/5 Schweitzer SEL-351 Relay Data: Inst. Overcurrent Pickup Range: 0.25–100.00 A, 0.01 A steps Time Overcurrent Pickup Range: 0.25–16.00 A, 0.01 A steps Time-Dial Range: 0.50–15.00, 0.01 steps (US Curves) Inverse Delay Curve: US-U4 (Extremely Inverse) selected. a) Specify an appropriate K-Link expulsion fuse for individual capacitor units based on IEEE Std 18 overload requirements. HINT:  The MMT curve fine print indicates that while the fuse melting curve starts well above the fuse’s nominal current rating, the fuse should not be overload on a normal basis without also derating it.   b) For the main breaker relays, specify settings for each of the relay functions indicated above. Clearly state your basis for each setting. HINT:  Recall that a relay must do two things – see faults AND carry the load.  Check to see if your 51 function can detect a rack fault (i.e. shorted series group).  With the 51 relay you may observe a peculiar difficulty with choosing a pickup setting which the 46 relay resolves.   c) The 51N-1, -2, -3 relays have dual pickup settings so specify settings for each of the relay functions indicated above. Clearly state your basis for each.  Note that all three relays will have identical settings.

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter10: System Protection
Section: Chapter Questions
Problem 10.27P
icon
Related questions
Question


Problem 1 – The 4.16kV distribution station capacitor bank below consists of 3 ungrounded double-wye (UGDY) stages with a main breaker connecting Stage 1 capacitors directly and with Stages 2 and 3 through vacuum switches.  

Capacitor Unit Ratings: 2.400kV, 200kVAR

CT Data: Main Breaker:  1500/5, Neutral CT:  50/5

Schweitzer SEL-351 Relay Data: Inst. Overcurrent Pickup Range: 0.25–100.00 A, 0.01 A steps

Time Overcurrent Pickup Range: 0.25–16.00 A, 0.01 A steps

Time-Dial Range: 0.50–15.00, 0.01 steps (US Curves)

Inverse Delay Curve: US-U4 (Extremely Inverse) selected.

a) Specify an appropriate K-Link expulsion fuse for individual capacitor units based on IEEE Std 18 overload requirements.

HINT:  The MMT curve fine print indicates that while the fuse melting curve starts well above the fuse’s nominal current rating, the fuse should not be overload on a normal basis without also derating it.

 

b) For the main breaker relays, specify settings for each of the relay functions indicated above. Clearly state your basis for each setting.

HINT:  Recall that a relay must do two things – see faults AND carry the load.  Check to see if your 51 function can detect a rack fault (i.e. shorted series group).  With the 51 relay you may observe a peculiar difficulty with choosing a pickup setting which the 46 relay resolves.

 

c) The 51N-1, -2, -3 relays have dual pickup settings so specify settings for each of the relay functions indicated above. Clearly state your basis for each.  Note that all three relays will have identical settings.

1500/5
ACB
1500/5
SIN
50/5
50 51
Wit
50 and SON relay pickup settings.
51 and 51N relay pickup and TD
settings, selecting the inverse curve
type as extremely inverse (SEL-U3).
• 46 (negative sequence overcurrent)
relay pickup and TD settings.
vs
SIN
46
LHF
SON-51N)
50/5
Vs
50/5
SIN
SIN-Alarm and 51N-Trip pickup settings with a 10 sec. definite delay.
Transcribed Image Text:1500/5 ACB 1500/5 SIN 50/5 50 51 Wit 50 and SON relay pickup settings. 51 and 51N relay pickup and TD settings, selecting the inverse curve type as extremely inverse (SEL-U3). • 46 (negative sequence overcurrent) relay pickup and TD settings. vs SIN 46 LHF SON-51N) 50/5 Vs 50/5 SIN SIN-Alarm and 51N-Trip pickup settings with a 10 sec. definite delay.
ELLE
M
IEEEEE
...
****
Nghe
O
SAC ELECTRIC COMPANY C
SAC ELECTRIC CANADALTO-
CENTERS
MINIMUM MELTING TIME-CURRENT CHARACTERISTIC CURVES
POSITROL FUSE LINKS-S&C "K" SPEED
11, AND ARE
PREFERRED RATING, K
42,2 MM, AND
ARE INTERMEDIATE
RATINGS
TOO NUMBER 165-6
Pa
Jary 2010
JI
T..
Transcribed Image Text:ELLE M IEEEEE ... **** Nghe O SAC ELECTRIC COMPANY C SAC ELECTRIC CANADALTO- CENTERS MINIMUM MELTING TIME-CURRENT CHARACTERISTIC CURVES POSITROL FUSE LINKS-S&C "K" SPEED 11, AND ARE PREFERRED RATING, K 42,2 MM, AND ARE INTERMEDIATE RATINGS TOO NUMBER 165-6 Pa Jary 2010 JI T..
Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 3 steps

Blurred answer
Knowledge Booster
HVDC
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning