The air in a theatre room must be 22 °C and the relative humidity 55%. The outdoor temperature is 30 °C and relative humidity 50%. There are 900 seats in the room and 25 m³/h of fresh air is reserved for each seat. Every attendant releases a heat load (sensible + latent) of 100 W and a moisture load of 80 g/h. The sum of heat loads from other than human sources is 20 kW. What must the supply air state be in order to maintain the indoor conditions mentioned above?

Principles of Heat Transfer (Activate Learning with these NEW titles from Engineering!)
8th Edition
ISBN:9781305387102
Author:Kreith, Frank; Manglik, Raj M.
Publisher:Kreith, Frank; Manglik, Raj M.
Chapter6: Forced Convection Over Exterior Surfaces
Section: Chapter Questions
Problem 6.8P
icon
Related questions
Question
The air in a theatre room must be 22 °C and the relative humidity 55%. The outdoor temperature is 30 °C and relative humidity 50%. There are 900 seats in the room and 25 m³/h of fresh air is reserved for each seat. Every attendant releases a heat load (sensible + latent) of 100 W and a moisture load of 80 g/h. The sum of heat loads from other than human sources is 20 kW. What must the supply air state be in order to maintain the indoor conditions mentioned above?
Expert Solution
steps

Step by step

Solved in 5 steps with 1 images

Blurred answer
Knowledge Booster
Convection
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, mechanical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Principles of Heat Transfer (Activate Learning wi…
Principles of Heat Transfer (Activate Learning wi…
Mechanical Engineering
ISBN:
9781305387102
Author:
Kreith, Frank; Manglik, Raj M.
Publisher:
Cengage Learning