. A commercial office building is to be supplied service at 208Y/120 V from the utilıty company 12.47 kV distribution feeder (12.47 kV line-to-line and 7.2 kV line-to- neutral). The estimated demand load is 85 kW at 0.9 lagging power factor. Determine the appropriate apparent power rating and voltage rating of the three-phase, pad-mounted transformer required to serve this load. The transformer is connected delta-grounded wye. Assume the load is continuous and allow a 25% factor for load growth.

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter2: Fundamentals
Section: Chapter Questions
Problem 2.26P: A small manufacturing plant is located 2 km down a transmission line, which has a series reactance...
icon
Related questions
Question
100%

Transformer Problem (see attached picture).  Use given tables (see attached picture).

TABLE 14-3
Standard kVA Ratings for Pad-
Mounted Transformers
Single Phase
Three Phase
25
75
37.5
112.5
50
150
75
225
100
300
167
500
750
1000
1500
2000
2500
Source: Reprinted from American National
Standard C57.12.21-1980 by permission of the
National Electrical Manufacturers Association.
TABLE 14-4
Standard Voltage Ratings for Pad-Mounted
Transformers
Single Phase
Three Phase
2400
4160GRDY/2400
8320GRDY/4800
4160
4800
12,000GRDY/6930
12,470GRDY/7200
13,200GRDY/7620
13,800GRDY/7970
16,430GRDY/9430
22,860GRDY/13,200
23,900GRDY/13,800
34,500GRDY/19,920
7200
12,000
12,470
13,200
13,800
16,340
22,860GRDY/13,200
23,900GRDY/13,800
24,940GRDY/14,400
34,500GRDY/19,920
208Y/120
240/120
240
480
480Y/277
Transcribed Image Text:TABLE 14-3 Standard kVA Ratings for Pad- Mounted Transformers Single Phase Three Phase 25 75 37.5 112.5 50 150 75 225 100 300 167 500 750 1000 1500 2000 2500 Source: Reprinted from American National Standard C57.12.21-1980 by permission of the National Electrical Manufacturers Association. TABLE 14-4 Standard Voltage Ratings for Pad-Mounted Transformers Single Phase Three Phase 2400 4160GRDY/2400 8320GRDY/4800 4160 4800 12,000GRDY/6930 12,470GRDY/7200 13,200GRDY/7620 13,800GRDY/7970 16,430GRDY/9430 22,860GRDY/13,200 23,900GRDY/13,800 34,500GRDY/19,920 7200 12,000 12,470 13,200 13,800 16,340 22,860GRDY/13,200 23,900GRDY/13,800 24,940GRDY/14,400 34,500GRDY/19,920 208Y/120 240/120 240 480 480Y/277
1. A commercial office building is to be supplied service at 208Y/120 V from the utilıty
company 12.47 kV distribution feeder (12.47 kV line-to-line and 7.2 kV line-to-
neutral). The estimated demand load is 85 kW at 0.9 lagging power factor. Determine the
appropriate apparent power rating and voltage rating of the three-phase, pad-mounted
transformer required to serve this load. The transformer is connected delta-grounded
wye. Assume the load is continuous and allow a 25% factor for load growth.
Transcribed Image Text:1. A commercial office building is to be supplied service at 208Y/120 V from the utilıty company 12.47 kV distribution feeder (12.47 kV line-to-line and 7.2 kV line-to- neutral). The estimated demand load is 85 kW at 0.9 lagging power factor. Determine the appropriate apparent power rating and voltage rating of the three-phase, pad-mounted transformer required to serve this load. The transformer is connected delta-grounded wye. Assume the load is continuous and allow a 25% factor for load growth.
Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 2 steps

Blurred answer
Knowledge Booster
Single phase transformer
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning