1. A 100-kVA distribution transformer has a maximum efficiency of 98 % at 50 % full-load and unity power factor. Determine its iron losses and full-load copper losses. The transformer undergoes a daily load cycle as follows : Load Power factor Load duration 100 kVA 1.0 8 hrs 50 kVA 0.8 6 hrs No load 10 hrs Determine its all-day efficiency. (Electrical Engineering, MS Univ. Baroda 1979)
Q: A 220 / 400 V, 7 kVA, 50 Hz single phase transformer has a full load copper loss of 102 W. Determine…
A: S = 7KVA 220/400 V 50Hz frequency PF =1 Load x= 1
Q: A load of 1400 KVA at 0.866 pf lagging is supplied by a 3-phase transformer of 1,000 KVA and 500 KVA…
A:
Q: 1. A 100-kVA distribution transformer has a maximum efficiency of 98 % at 50 % full-load and unity…
A: Efficiency η=98% power factor cosϕ=1
Q: A transformer takes a current of 0.8A, when its primary is connected to a 240V, 50Hz supply, the…
A: Transformers
Q: The primary and secondary windings of a 500 kVA transformer have resistances of 0.44 Ω and 0.0027 Ω,…
A: The solution is given below
Q: A 1-phase transformer, 15 kVA, 660/250V, 50HZ, Reg1= 2.78790 and Xegi = 5.57572. %3D the secondary…
A: According to the question, we have to calculate the value of regulation up at full load and power…
Q: 2) The following no-load results are obtained at the excitation branch of a 10, 20 kVA, 2400/240 V,…
A:
Q: Q29. A 800 kVA transformer has a primary winding resistance of 0.8Ω and a secondary winding…
A:
Q: 300kVA transformer has primary and secondary winding resistances of 0.5Ω, and 0.0015Ω respectively.…
A: First we will find total total secondary resistance and than copper losses at 40%load. Cupper losses…
Q: Example: A 50 kVA distribution transformer has iron loss of 600W and full-load copper loss of 700W.…
A: A transformer is an electrical machine which is used in AC circuit to either step up or step down…
Q: 23 Given a 100 kVA, 50 Hz power transformer. The maximum efficiency of the transformer is 97.5 %…
A: Transformer: An device used in the transfer of electric energy is a transformer. AC current is used…
Q: A 25 kVA, 2400/240-V, single phase transformer has an equivalent impedance referred to the primary…
A: Given- Power of a transformer= 25kVA voltage=2400/240-V core loss= 120 W power factor= 0.85…
Q: Calculate the daily efficiency of a single-phase transformer with an output capacity of 350 kVA at…
A: In this question we need to find a all day efficiency of the given transformer
Q: A single phase transformer takes 10 A on no load at p.f. of 0.2 lagging. The turns ratio is 4: 1…
A: We have a single phase transformer having, No-load current (I) = 10 A Power factor (Cos ϕ0) = 0.2…
Q: A 750 kVA transformer is at full load with an overall power factor of 0.65 lagging. The power factor…
A: By adding capacitor we supply reactive power to the load , so source has to deliver less reactive…
Q: A 400 kVA transformer has a primary winding resistance of 0.5 2 and a secondary winding resistance…
A:
Q: Example 33.3. A 3-phase, 6,600/415-V, 2,000-kVA transformer has a per unit resistance of 0.02 and a…
A: Given data, Load KVA = 200 kVA Per unit resistance, Rpu=0.02 Per unit reactance Xpu=0.1 Power…
Q: Calculate the daily efficiency of a single-phase joule with an output power of 350 kilovolts-ampere…
A:
Q: A 220/400 V, 10 KVA, 50 Hz, single phase transformer has copper loss of 120 W at full load. If it…
A: η x = xkVA×100×cosϕ xkVA×100×cosϕ+Pi+x2Pc×10098 = 1x10x1000x11x10x1000x1+Pi+1x1x120 x 100Pi =…
Q: The maximum efficiency of a 500 kVA, 3300/500 volts, 50 Hz, single - phase transformer is 97 % and…
A:
Q: 43. A 250KVA, 2000/400V, single phase transformer achieved its variable loss equal to its fixed loss…
A: Given information about a single phase transformer: Rated power S=250 KVA. The induced EMF ratio is…
Q: QI/A 100-kVA distribution transformer has a maximum efficiency of 98 % at 50 % full- load and unity…
A: TRANSFORMER: The transformer transfers power from one circuit to another circuit without a change…
Q: A 1 MVA (1 Mega VA) single phase transformer is connected as an auto transformer as follows. Between…
A:
Q: The maximum efficiency of a 500 – kVA, 3300/500 V, 50 Hz, single phase transformer is 97% and occurs…
A: Given maximum efficiency ηmax=97% at 3/4 of full load kVA rating of transformer =500kVA impedance…
Q: Day loading duty-cycle profile of a 100 kVA, 2400/240 V, 50 Hz transformer is given below. The SC…
A: By definition, the all-day efficiency of a transformer is given by: ηall-day=Output kWh in 24…
Q: The following results were obtained on a 50 kVA transformer. Open circuit test – primary voltage,…
A: TRANSFORMER: The transformer transfers power from one circuit to another circuit without a change…
Q: 10- A 10-KVA, 500/250-V, single-phase transformer has its maximum efficiency of 94 % when delivering…
A:
Q: A 20 kVA, 220 V / 110 V, 50 Hz single phase transformer has full load copper loss = 200W and core…
A:
Q: 2. A 50-kVA distribution transformer has full-load efficiency at 1.0 power factor of 96%, the copper…
A: Given data, Rating of transformer S =50 KVA Efficiency η=96% Copper loss Pcu=Iron loss Pi Power…
Q: Power transformer A, has Rated power of 150MVA. Line voltage of 330/66 kV Frequency=50Hz Connection…
A: Active Power across the Load = Apparent Power ×power factor ---- 1) Putting value in equation -1)…
Q: A 125 kVA transformer having a primary voltage of 2200 V at 50 Hz has 182 primary turns and 40…
A: As per the guidelines of Bartley we supposed to answer first question only since both question are…
Q: Question 1 A 132/33 kV 250 MVA single-phase step-down transformer has the following parameters: R1 =…
A:
Q: 47. A 150-kVA single-phase transformer has a core loss of 1.5 kW and a full-load Cu loss of 2 kW.…
A:
Q: a three-phase step-down transformer with 150 kVA, 2080/208 V 60 Hz Y / Y connected R1 = 0.45 ohm, X1…
A:
Q: A transformer rated at 1000 kVA is operating near capacity as it supplies a load that draws 900 kVA…
A: According to the question, we have to find, real power delivered to the load and how mu ch…
Q: A three phase 110 kVA ,50 Hz, 3300/420.89 V, delta-star transformer. The transformer has a primary…
A: Given data about the three phase delta-star connected transformer is: Emf induced in primary…
Q: (b) The followings are the reading of the test on a transformer. Transformer rating 10 kVA 240/480…
A: In this question, Transformer rating is given 10kVA, 0.866Power factor, 240/480V Open and short…
Q: Consider a 25-kVA, 400/1600 V single-phase transformer supplying full-load current at 0.85 lagging…
A:
Q: determine (i) the core loss current(Ic) (ii) the power factor on no-load and (iii) the magnetizing…
A: Given,the measurement is taken while the secondary of transformer is open circuited. So we can say…
Q: Example 32.72. A 300-kVA, single-phase transformer is designed to have a resistance of 1.5% and…
A:
Q: A 15 KVA, 10.8 KV/240-V, 60 Hz, single-phase conventional transformer is supplying 10 KW of power to…
A:
Q: A 10KVA single-phase transformer provides a no-load secondary voltage of 110 volts. If the…
A:
Q: 31. The all-day efficiency of a transformer dep primarily on (a) its copper loss (b) the amount of…
A: Auto transformer features More KVA Rating Less Cu matetial used More efficiency Less insulation…
Q: Determine the efficiency of a 150 kVA transformer at 50% of full load and 0.8 power factor lagging…
A:
Q: Example: A 50 kVA distribution transformer has iron loss of 600W and full-load copper loss of 700w.…
A:
Q: A single-phase transformer is rated at 2 kVA, 240/120 V. The transformer is fully loaded by an…
A: The rating of the transformer is given as:
Q: efficiency of a 200 KVA, single phase transformer is 98.78 % when delivering full load at 0.8 power…
A: In this question we will find iron loss and full load cu loss...
Q: "A 500-turns auto transformer, operating in the step-down mode with 20 percent tap supplies a 6.6…
A: in auto transformer transformer action takes place between two windings. transformed VA=product of…
Q: Calculate the daily efficiency of a single-phase transformer with an output capacity of 350 kVA at…
A: “Since you have posted a question with multiple sub-parts, we will solve first four subparts for…
Q: The primary and secondary windings of a 40 kVA, 6600/250 V single-phase two-winding transformer have…
A: The primary and secondary windings 40 kVA, 6600/250 V single-phase two-winding transformer…
Step by step
Solved in 3 steps with 2 images
- A single-phase 100-kVA,2400/240-volt,60-Hz distribution transformer is used as a step-down transformer. The load, which is connected to the 240-volt secondary winding, absorbs 60 kVA at 0.8 power factor lagging and is at 230 volts. Assuming an ideal transformer, calculate the following: (a) primary voltage, (b) load impedance, (c) load impedance referred to the primary, and (d) the real and reactive power supplied to the primary winding.A two-winding single-phase transformer rated 60kVA,240/1200V,60Hz, has an efficiency of 0.96 when operated at rated load, 0.8 power factor lagging. This transformer is to be utilized as a 1440/1200-V step-down autotransformer in a power distribution system. (a) Find the permissible kVA rating of the autotransformer if the winding currents and voltages are not to exceed the ratings as a two-winding transformer. Assume an ideal transformer. (b) Determine the efficiency of the autotransformer with the kVA loading of part (a) and 0.8 power factor leading.The transformer of Problem 3.16 is supplying a rated load of 50 kVA at a rated secondary voltage of 240 V and at 0.8 posr factor lagging. Neglect the transformer exciting current. (a) Determine the input terminal voltage of the transformer on the high-voltage side. (b) Sketch the corresponding phasor diagram. (c) If the transformer is used as a step-down transformer at the load end of a feeder whose impedance is 0.5+j2.0, find the voltage VS and the power factor at the sending end of the feeder.
- The motors M1andM2 of Problem 3.45 have inputs of 120 and 60 MW, respectively, at 13.2 kV, and both operate at unity power factor. Determine the generator terminal voltage and voltage regulation of the line. Neglect transformer phase shifts.1) A single-phase 100-kVA, 2,400/240 V, 60-Hz distribution transformer is used as a step-down transformer. The load, which is connected to the 240 V secondary winding, absorbs 80 kVA at 0.8 power factor lagging and is at 230 V. Assuming an ideal transformer, calculate the following: (a) primary voltage;(b) load impedance;(c) load impedance referred to the primary;(d) the active and reactive power supplied to the primary winding.A simple power system is shown in this Fig. The generator (480 V, 10 kVA) is connected to an ideal step-up transformer (1:10), a transmission line (R=20 Ohm and X=60 Ohm), step down transformer (20:1) and a load with magnitude Z=10 Ohm and angle =30 degree the base values for this system are chosen to be 480 V and 10 kVA at the generator. Calculate the per-unit impedance of the load. Select one: a. 1736 (45 degree) Ohm b. 36 (90 degree) Ohm c. 1.736 (30 degree) Ohm d. None of the above
- In a three-phase step-down transformer with 150 kVA, 2080/208 V 60 Hz Y / Y connected R1 = 0.45 ohm, X1 = 2.2 ohm, R2 = 4.5 mohm, X2 = 22 mohm, Rc = 10 kohm, Xm = 8 kohms. When installed at 120 kVA, 90 kW back power factor, if the voltage at the load ends is at its nominal value, a) Primary side terminal voltage b) Yield (efficiency) c) Calculate the voltage regulation value?A 2,300/240-V, 60-Hz, 4.6-kVA transformer isdesigned to have an induced emf of 2.5 V/turn.Assuming an ideal transformer, finda. The numbers of high-side turns Nh and low-sideturns Nl .b. The rated current of the high-voltage side Ih.c. The transformer ratio when the device is used as astep-up transformer.2) A three -phase transformer of 90 kVA, 13200/480 V (line to line), with connection Delta-Delta, has a resistance of 1.3% and a reactance of 8.2% per unit. a) Calculate the phase impedance of the transformer referred to the high side strain. b) Calculate the phase impedance of the transformer referred to the low side strain. c) Calculate the transformer voltage regulation into nominal conditions with F.P.0,8 in delay.
- A.1. A gas likely to be used in an inert-gas system of a power transformer isA. oxygen.B. hydrogen.C. air.D. nitrogen.A.2. In the design of transformer windings, creepage between conductors and core yokes is prevented byproviding,A. keep-back distance.B. vertical oil ducts.C. separation sticks.D. bushing terminals.A Transformer with 10:1 ratio and rated at 50-kVA, 2400/240-V, 50-Hz is used to step down the voltage of a distribution system. The low-tension voltage is to be kept constant, if the transformer has: R = 2.2 0, R2 = 0.014 Q, X, = 4.1 0, X2 = 0.03 0, then, a. What load impedance connected to low-tension side will be loading the transformer fully. b. Calculate the equivalent resistance as referred to primary. c. Calculate the equivalent reactance as referred to primary. d. Calculate the equivalent impedance as referred to primary. e. Calculate the total Cu loss.A 20-kVA 8000/277-V distribution transformer has the following resistances and reactance: RP = 32 Ω RS = 0.05Ω X P = 45Ω XS = 0.06Ω RC = 250 kΩ X M = 30 kΩ The excitation branch impedances are given referred to the high-voltage side of the transformer. (a) Find the equivalent circuit of this transformer referred to the high-voltage side. (b) Find the per-unit equivalent circuit of this transformer. (c) Assume that this transformer is supplying rated load at 277 V and 0.8 PF lagging. What is this transformer’s input voltage? What is its voltage regulation? (d) What is the transformer’s efficiency under the conditions of part (c)?