43. A 250KVA, 2000/400V, single phase transformer achieved its variable loss equal to its fixed loss at 80% of its full load at its lagging pf showing the value of 0.76. Calculate the efficiency of the transformer at 0.8pf leading at one half of its full load. Also, calculate load dependent losses , iron losses at full load and total associated losses when connected to the system
Q: 120/480 V, 10 kVA two-winding transformer is to be used as an auto-transformer to supply a 480 V…
A:
Q: A 10 kVA, 2400/240 V, 60 Hz single phase transformer has Z, = 5.2 + j12.5 ohms and Z2 = 0.06 + j0.12…
A: In this question, We need to calculate the load voltage if Primary voltage and frequency is rated.…
Q: A single-phase transformer rated 75kVA, 8000/240V is given the short circuit test. With the…
A: Rated current in primary side =75*1038000=9.375 amp Short circuit test is done with secondary side…
Q: 2. A single-phase transformer has a rating of 100KVA, 7200V/600V, 60HZ. a. If it is reconnected as…
A:
Q: The efficiency of a 20 kVA 15.4 / 0.4 kV three-phase power transformer is 79.1% for a load with unit…
A: Given: For a 20 kVA, 15.4/0.4 kV, 3-phase star-delta transformer, Relative idle or no-load %I0=30,…
Q: Example 33.5. A 3-phase transformer, ratio 33/6.6-kV, A/Y, 2-MVA has a primary resistance of 8 per…
A:
Q: b) A single-phase transformer with 10: 1 turns-ratio and rated at 50 kVA, 2400-V/240-V, 50-Hz is…
A: (b): Given in the question: Turns ratio: N1N2=101 Voltage on the primary side is: V1 = 2400V Voltage…
Q: iii. No-load current 3. If the ratio of V/F has been kept constant and the observed value of…
A: Q.1) Explanation 1)When the frequency is lowered (for slower motor speed), the magnetic field…
Q: Q2) A 140-kVA, 7500/277-V distribution transformer has the following resistances and reactances: R,…
A: As per the guidelines of Bartley we supposed to answer first three subpart only.
Q: Calculate the daily efficiency of a single-phase transformer with an output capacity of 350 kVA at…
A: In this question we need to find a all day efficiency of the given transformer
Q: An 11,000/230-V, 150-kVA, 50-Hz, 1-phase transformer has a core loss of 1.4 kW and full-load Culoss…
A: In this question , transformer cu loss and iron loss given..Output KVA given..We have to find out…
Q: Compute the copper losses at full load if a 500KVA transformer has 90% efficiency at both half-load…
A:
Q: a) What is the complex power drawn and delivered by the transformer? (b) Draw a per-phase equivalent…
A:
Q: A single-phase, 2,959 VA, 2200/220 transformer has the following open circuit and short circuit test…
A: 'Since you have asked multiple questions, we will solve the first question for you. If you want any…
Q: 4.6 A 60 Hz, 75 kVA, 2400/240 V, single-phase transformer is used to step down the voltage of a…
A:
Q: A 10-kVA, 2000/400-V, single-phase transformer has resistances and leakage reactances as follows :…
A: The information we have : Primary voltage, V1 = 2000 V Secondary voltage, V2 = 400 V So,…
Q: Three single phase transformers, each rated at 12kVA, 120/240V, 60Hz, are connected to form a…
A: Given data : Each rating of transformer =12 KVA Power factor =0.8 lagging
Q: (b) A 50-kVA, 2600/1300-V, single-phase transformer has a core loss of 780 W. The transformer has a…
A:
Q: QI An 11,000/230-V, 150-kVA, 50-Hz, 1-phase transformer has a core loss of 1.4 kW and full-load…
A: Given data: Core loss = 1.4 kW Full load Copper loss= 1.6 kW Full load KVA =150 Power factor…
Q: Consider a single phase transformer of rating 150 KVA, 3600/360, 50 Hz. Let the series resistance…
A: Formula to calculate voltage required to produce rated current at short circuit is: VSC=V1×ZPUwhere…
Q: The efficiency of a 400 kVA, 1-phase transformer is 95 % when delivering full load at 0.8 power…
A:
Q: Question # 2: A 2000/400 V, 100 kVA, 60 Hz step-down single-phase transformer has a primary and…
A:
Q: Problem 2. A 150-MVA, 220/22-kV, three-phase has the following parameters (in 2): R2 = 0.001 X, =…
A: In the question, All parameters are given of transformer. Determine the equivalent circuit…
Q: Consider a single phase transformer of rating 150 KVA, 1500/150, 50 Hz. Let the series resistance…
A: Given: Z1=R1+jX1=0.2+j0.45 ΩZ2=R2+jX2=0.002+j0.0045 ΩKVA=150
Q: 1. A 40-MVA, 20/400 kV, single-phase transformer has the following series impedances: ZLV = 0.9 +…
A: Introduction: An equivalent Transformer Circuit is an explanation of the transformer's behavior by…
Q: 1. (a) The diagram for a single phase 60 MVA transformer is given below. Convert it to a Step-down…
A: Given 2-winding transformer details are V1/V2=50/100 kV.S=60 MVA The input and output currents of…
Q: 33. The efficiency of a 400 kVA, 1-phase transformer is 98.77 % when delivering full load at 0.8…
A: Here we discuss about the efficiency calculations of transformer. NOTE:- As in this 1 Q., 2…
Q: Rated values of an ideal single-phase transformer; 3000VA, 380V/220V’ tour. If the network frequency…
A:
Q: Q/ The efficiency of a 400-kVA, single-phase, 60-Hz transformer is 98.77% when delivering full-load…
A:
Q: The transformer shown operates at 50Hz with the turn numbers N1=200 and N2=100 for primary and…
A:
Q: 4.1 Assume that an ideal transformer used to step down 13.8–2.4kV and that it is fully loaded when…
A: Given:Transormer is ideal,Hence, the i/p KVA = o/p KVAVoltage rating 13.8 kV/ 2.4 kVAlso, o/p KVA =…
Q: A 150-kVA single-phase transformer has a core loss of 1.5 kW and a full-load Cu loss of 2 kW.…
A:
Q: A transformer of 100MVA, 60Hz, 138/69 kV, works as step down, has the following parameters: r1 =…
A:
Q: A 1-phase transformer, 12 kVA, 600/200V, 50Hz, Short-circuit (high voltage data): 120V, 20A and…
A:
Q: A 10-kVA, 450/120V, 50-Hz transformer has the following circuit parameters: R, = 0.12 n, R, = 8.533…
A: As per Bartleby guidelines, since you have posted a question with multiple sub-parts, we will solve…
Q: A 600 kVA, 1-phase transformer has an efficiency of 92 % both at full-load and half- load at unity…
A: Given, Output kVA rating = 600 kVA Efficiency, η=92 % (both at full-load and half-load) Power…
Q: Q2: A 4000/400 V, 10 kVA transformer has the following constants: Primary and secondary winding…
A:
Q: A 11000/230 V, 150-kVA, 1-phase, 50-Hz transformer has core loss of 1.4 kW and full load copper loss…
A: The solution is given below
Q: A 150-kVA simple-phase transformer has a core loss of a 1.5kW and a full-load Cu loss of 2 kW.…
A: In this question we need to find a efficiency of the transformer at the given condition.
Q: Here is a single phase transformer, 15 kVA, 15000/380 V, 50 Hz has Ze-0.02+j0.05 perunit, R. 50…
A:
Q: Example 10. A 3300/230 V, 50-kVA, transformer is found to have impedance of 4% and a Cu loss of 1.8%…
A: In this question we will find percentage reactance and ohmic value of resistance , reactance and…
Q: . A 15kVA single-phase transformer, for 10000V/440V at no load, has resistances and leakage…
A: In this question, We need to determine the value of the secondary voltage at full load, 0.85 power…
Q: A single-phase ideal transformer is rated at 2KVA, 240V/120V. The transformer is supplying rated…
A: A single phase transformer has, Apparent power (S) = 2 kVA Voltage ratio is 240/120 V. Load…
Q: ratio
A:
Q: A 5000-KVA 230/13.8-kV single-phase power transformer has a per-unit resistance of 1 percent and a…
A: In this question we need to find a equivalent circuit referred to LV side of transformer , voltage…
Q: A 100,000-kVA 230/115-kV ∆-∆ three-phase power transformer has a per-unit resistance of 0.02 pu and…
A: Given Data Rating 100,000-kVA 230/115-kV Type : ∆-∆ three-phase per-unit resistance = 0.02 pu…
Q: A 240-kVA, 480/4800-V, step-up transformer has the following constants: Rs = 2.5 Ω, Xs = j5.75 Ω, Rp…
A: Given step up Transformer with240 KVA, 480/4800 vRs=2.5 Ω,Xs=j5.75 ΩRp=25 mΩ,Xp=j57.5 ΩThe core…
Q: Calculate the daily efficiency of a single-phase transformer with an output capacity of 350 kVA at…
A: “Since you have posted a question with multiple sub-parts, we will solve first four subparts for…
Q: 2. A 4800/240-V, single phase transformer is rated at 10 kVA. It has an equivalent impedance…
A: Features: Transformer is a static device which transfers power from one circuit to another circuit…
please answer in short....please dont reject i willl like answer in short...
Step by step
Solved in 4 steps
- A two-winding single-phase transformer rated 60kVA,240/1200V,60Hz, has an efficiency of 0.96 when operated at rated load, 0.8 power factor lagging. This transformer is to be utilized as a 1440/1200-V step-down autotransformer in a power distribution system. (a) Find the permissible kVA rating of the autotransformer if the winding currents and voltages are not to exceed the ratings as a two-winding transformer. Assume an ideal transformer. (b) Determine the efficiency of the autotransformer with the kVA loading of part (a) and 0.8 power factor leading.A single-phase 50-kVA,2400/240-volt,60-Hz distribution transformer is used as a step-down transformer at the load end of a 2400-volt feeder whose series impedance is (1.0+j2.0) ohm. The equivalent series impedance of the transformer is (1.0+j2.5) ohms referred to the high-voltage (primary) side. The transformer is delivering rated load at a 0.8 power factor lagging and at a rated secondary voltage. Neglecting the transformer exciting current, determine (a) the voltage at the transformer primary terminals, (b) the voltage at the sending end of the feeder, and (c) the real and reactive power delivered to the sending end of the feeder.Consider Figure 3.4. For an ideal phase-shifting transformer, the imda nce is unchanged when it is referred from one side to the other. (a) True (b) False
- A single-phase, 50-kVA,2400/240-V,60-Hz distribution transformer has the following parameters: Resistance of the 2400-V winding: R1=0.75 Resistance of the 240-V winding: R2=0.0075 Leakage reactance of the 2400-V winding: X1=1.0 Leakage reactance of the 240-V winding: X2=0.01 Exciting admittance on the 240-V side =0.003j0.02S (a) Draw the equivalent circuit referred to the high-voltage side of the transformer. (b) Draw the equivalent circuit referred to the low-voltage side of the transformer. Show the numerical values of impedances on the equivalent circuits.An infinite bus, which is a constant voltage source, is connected to the primary of the three-winding transformer of Problem 3.53. A 7.5-MVA,13.2-kV synchronous motor with a sub transient reactance of 0.2 per unit is connected to the transformer secondary. A5-MW,2.3-kV three-phase resistive load is connected to the tertiary Choosing a base of 66 kV and 15 MVA in the primary, draw the impedance diagram of the system showing per-unit impedances. Neglect transformer exciting current, phase shifts, and all resistances except the resistive load.Consider Figure 3.25 of the text for a transformer with off-nominal turns ratio. (i) The per-unit equivalent circuit shown in part (c) contains an ideal transformer which cannot be accommodated by some computer programs. (a) True (b) False (ii) In the - circuit representation for real c in part (d), the admittance parameters Y11 and Y12 would be unequal. (a) True (b) False (iii) For complex c, can the admittance parameters be synthesized with a passive RLC circuit? (a) Yes (b) No
- The transformer of Problem 3.16 is supplying a rated load of 50 kVA at a rated secondary voltage of 240 V and at 0.8 posr factor lagging. Neglect the transformer exciting current. (a) Determine the input terminal voltage of the transformer on the high-voltage side. (b) Sketch the corresponding phasor diagram. (c) If the transformer is used as a step-down transformer at the load end of a feeder whose impedance is 0.5+j2.0, find the voltage VS and the power factor at the sending end of the feeder.PowerWorid Simulator case Problem 3_60 duplicates Example 3.13 except that a resistance term of 0.06 per unit has been added to the transformer and 0.05 per unit to the transmission line. Since the system is no longer lossless, a field showing the real power losses has also been added to the oneline. With the LTC tap fixed at 1.05, plot the real power losses as the phase shift angle is varied from 10 to +10 degrees. What value of phase shift minimizes the system losses?Consider a source of voltage v(t)=102sin(2t)V, with an internal resistance of 1800. A transformer that can be considered as ideal is used to couple a 50 resistive load to the source. (a) Determine the transformer primary-to-secondary turns ratio required to ensure maxi mum power transfer by matching the load and source resistances. (b) Find the average power delivered to the load, assenting maximum power transfer.
- A single-phase two-winding transformer rated 90MVA,80/120kV is to be connected as an autotransformer rated 80/200kV. Assume that the transformer is ideal. (a) Draw a schematic diagram of the ideal transformer connected as an autotransformer. showing the voltages, currents, and dot notation for polarity. (b) Determine the permissible kVA rating of the autotransformer if the winding currents and voltages are not to exceed the rated values as a two-winding transformer. How much of the kA rating is transferred by magnetic induction?The ratings of a three-phase three-winding transformer are Primary(1): Y connected 66kV,15MVA Secondary (2): Y connected, 13.2kV,10MVA Tertiary (3): A connected, 2.3kV,5MVA Neglecting winding resistances and exciting current, the per-unit leakage reactances are X12=0.08 on a 15-MVA,66-kV base X13=0.10 on a 15-MVA,66-kV base X23=0.09 on a 10-MVA,13.2-kV base (a) Determine the per-unit reactances X1,X2,X3 of the equivalent circuit on a 15-MVA,66-kV base at the primary terminals. (b) Purely resistive loads of 7.5 MW at 13.2 kV and 5 MW at 2.3kV are connected to the secondary and tertiary sides of the transformer, respectively. Draw the per- unit impedance diagram, showing the per-unit impedances on a 15-MVA,66-kV base at the primary terminals.A 130-MVA,13.2-kV three-phase generator, which has a positive-sequence reactance of 1.5 per unit on the generator base, is connected to a 135-MVA,13.2/115Y-kV step-up transformer with a series impedance of (0.005+10.1) per unit on its own base. (a) Calculate the per-unit generator reactance on the transformer base. (b) The load at the transformer terminals is 15 MW at unity power factor and at 115 kV Choosing the transformer high-side voltage as the reference phasor, draw a phasor diagram for this condition. (C) For the condition of part (b), find the transformer low-side voltage and the generator internal voltage behind its reactance. Also compute the generator output power and power factor.