2. A 3-phase, 75 MVA, 11-8 kV star-connected alternator with a solidly earthed neutral point has th lowing p.u. impedances based on rated phase voltage and rated phase current : Positive phase sequence impedance j2 p.u. Negative phase sequence impedance j0-16 p.u. j 0-08 p.u. Zero phase sequence impedance Determine the steady-state fault current for the following : (i) 3-phase symmetrical short-circuit (i line-to-earth fault (iii) two line-to-earth fault. The generated e.m.f. per phase is equal to the rated vo [(01840 A (ii) 4920 A (iii) 35

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter8: Symmetrical Components
Section: Chapter Questions
Problem 8.32P
icon
Related questions
Question
100%
2. A 3-phase, 75 MVA, 11-8 kV star-connected alternator with a solidly earthed neutral point has the fol-
lowing p.u. impedances based on rated phase voltage and rated phase current :
Positive phase sequence impedance
j2 p.u.
j0-16 p.u.
j0-08 p.u.
Negative phase sequence impedance
Zero phase sequence impedance
Determine the steady-state fault current for the following : (i) 3-phase symmetrical short-circuit (ii) one
line-to-earth fault (iii) two line-to-earth fault. The generated e.m.f. per phase is equal to the rated voltage.
[(i)1840 A (ii) 4920 A (iii) 3580 A]
3. The per unit values of positive, negative and zero sequence reactances of a network at fault are 0-08, 0-07
and 0-05 respectively. Determine the fault current if fault is line-to-line-to-ground.
j 16 p.u.]
Transcribed Image Text:2. A 3-phase, 75 MVA, 11-8 kV star-connected alternator with a solidly earthed neutral point has the fol- lowing p.u. impedances based on rated phase voltage and rated phase current : Positive phase sequence impedance j2 p.u. j0-16 p.u. j0-08 p.u. Negative phase sequence impedance Zero phase sequence impedance Determine the steady-state fault current for the following : (i) 3-phase symmetrical short-circuit (ii) one line-to-earth fault (iii) two line-to-earth fault. The generated e.m.f. per phase is equal to the rated voltage. [(i)1840 A (ii) 4920 A (iii) 3580 A] 3. The per unit values of positive, negative and zero sequence reactances of a network at fault are 0-08, 0-07 and 0-05 respectively. Determine the fault current if fault is line-to-line-to-ground. j 16 p.u.]
Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 2 steps with 1 images

Blurred answer
Knowledge Booster
Synchronous Generator
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning