Three single-phase two-winding transformers,

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter8: Symmetrical Components
Section: Chapter Questions
Problem 8.38P
icon
Related questions
Question

Three single-phase two-winding transformers, each rated 400 MVA, 13.8/ 199.2 kV, with leakage
reactance Xeq = 0.10 per unit, are connected to form a three-phase bank. Winding resistances and
exciting current are neglected. The high-voltage windings are connected in Y. A three-phase load
operating under balanced positive-sequence conditions on the high-voltage side absorbs 1000 MVA at
0.90 p.f. lagging, with VAN = 199.2 ∠00 kV. Determine the voltage Van at the low-voltage bus if the lowvoltage windings are connected
a) in Y,