Problem 2. A 150-MVA, 220/22-kV, three-phase has the following parameters (in 2): R2 = 0.001 X, = 0.002 R, = 0.1 X= 7800 X, = 0.25 R = 30250 The transformer is operating in step-down mode and delivering hafl of rated load at 22.5kV and 0.86 power factor lagging. a) Determine the equivalent circuit referred to the high-voltage side; b) Find the primary voltage and current; c) Determine the voltage regulation. d) Determine the efficiency.
Q: Consider a bank of three single-phase two-winding transformers whose high-voltage terminals are…
A: Two connected windings on the same core are modelled by the single-phase two-winding transformer.…
Q: A 200 – MVA, 15/200 kV single-phase power transformer has a per – unit resistance of 1.2 percent…
A: Part (1): Consider the base voltage to be 15 V and the base MVA to be 200 MVA. Since the base…
Q: The full load voltage drop in a single phase transformer are 2% and 4% due respectively to…
A: Given values are - Voltage dropR%=2%%R=2%Voltage dropX%=4%%X=4%
Q: Consider a single phase 2-winding 150 kVA, 2400/240 V, 60 Hz transformer with Reg = 0.00425 N, Xeq =…
A: In this question, Find the efficiency of the transformer If it's operated at rated current and…
Q: Q2. (a) Explain what is per unit system? What are the advantages of per-unit computations? Prove for…
A: Per unit system:-Per unit system is the value expressing system used in an electrical Power systems…
Q: laggin Hw2.1-3: Derive the following: • The Cu saving for step-up auto transformer with drawing. •…
A:
Q: The efficiency of transformer is maximum at 10O0% loading? * True False
A: The given statement is a false statement.
Q: A single-phase transformer bank has a rating of 30 MVA, 132kV/33 kV. By referring to the standard…
A: Given data, Rating of transformer P = 30 MVA Primary voltage Vp= 132 kV Secondary Voltage Vs=33 kV…
Q: A 40000-KVA, 25000-V/600-kV, single phase transformer has the following series impedances: Z1=…
A:
Q: A single phase transformer with 50 kVA, 2400V/240V, 50 Hz; Idle operating voltage 2400V, idle…
A:
Q: a) What is the complex power drawn and delivered by the transformer? (b) Draw a per-phase equivalent…
A:
Q: For a conceptual single-phase phase-shifting transformer, the primary voltage leads the secondary…
A: Note: As per our policy, I have attempted the first three subquestions. Given data: E1=E2+308E2=277…
Q: What's The relation between turn ratio current ratio annd voltage ratio(if it exists) for single…
A: The transformer is a static device that steps up or steps down the voltage depending upon the turn…
Q: Data from short-circuit and open-circuit tests of a 25-kVA, 6900-230 V, 60 Hz transformer are given…
A:
Q: The diagram for a single phase 60 MVA transformer is given below. Convert it to a Step-down…
A: In this question , we will convert single phase transformer into step down auto transformer..
Q: Consider a single phase transformer of rating 150 KVA, 3600/360, 50 Hz. Let the series resistance…
A: Formula to calculate voltage required to produce rated current at short circuit is: VSC=V1×ZPUwhere…
Q: The per-unit system calculations method allows to: Select one: O a. eliminate the need for explicit…
A: Most of human energy requirement is meet by generating electrical energy. Once electrical energy is…
Q: 9. While conducting short short circuit test in a transformer, which side is short circuited?
A: We are authorized to answer one question at a time, since you have not mentioned which question you…
Q: 2-37/13* A 50-kVA, 2300-230-V, 60-Hz transformer supplies a 0.8 lagging power- factor load whose kVA…
A: Solution Given, cos θ = 0.8 core loss= 0.42…
Q: Discuss the potential transformer with neat schematic diagram.
A:
Q: (a) (i) List categories of transformer. (ii) What are the losses that need to be considered when…
A: Transformer used to transfer energy from one device to another and it works on the faraday's law of…
Q: Two generators are connected in parallel to the low voltage side of a transformer. Generators Gl and…
A: converting old sub-transient of generator at new base value Xpu new =Xpu old MVAnewMVAold…
Q: Consider a single phase transformer of rating 150 KVA, 1500/150, 50 Hz. Let the series resistance…
A: Given: Z1=R1+jX1=0.2+j0.45 ΩZ2=R2+jX2=0.002+j0.0045 ΩKVA=150
Q: A 200 – MVA, 15/200 kV single-phase power transformer has a per – unit resistance of 1.2 percent and…
A:
Q: 1. (a) The diagram for a single phase 60 MVA transformer is given below. Convert it to a Step-down…
A: Given 2-winding transformer details are V1/V2=50/100 kV.S=60 MVA The input and output currents of…
Q: Three single-phase two-winding transformers, each rated 25 MVA, 54.2/5.42 kV, are connected to form…
A: The explanation is as follows.
Q: Q4(b) A 200-MVA 15/200-kV single-phase power transformer has a per-unit resistance of 1.2 percent…
A: Firstly the exact equivalent model of a transformer is as shown below:
Q: The hysteresis and eddy-current losses for a 75-kVA, 480-120 V, 60-Hz transformer are 215 W and I 15…
A: find the explanation below
Q: 3. A 10 kVA, single-phase transformer has a turns ratio of 15:1 and is supplied from a 2,0 kV…
A: Single phase transformer 10KVA , turn ratio 15:1 Primary side voltage 2KV Find the secondary…
Q: Three Phase Transformer connections: Discuss Fully the various methods available for transforming…
A: The methods of transformation of a 3-phase voltage into higher or lower 3-phase voltages is done…
Q: A lø transformer has an equivalent leakage reactance of 0.04 per unit. The full-load copper loss is…
A:
Q: The following test data were obtained from short-circuit and open-circuit tests of a 50-kVA,…
A: Given data Apparent power is S = 50 kVA Voltage is V = 600 V frequency is f = 60 Hz a) Calculating…
Q: The figure below shows the equivalent circuit of a nominal 240V-120V, 1000 VA, single-phase…
A:
Q: A 37.5-kVA, 6900-230-V, 60-Hz, single-phase transformer is operating in the step-down mode at rated…
A: a) Given data Apparent power is S = 37.5 KVA Low side voltage is VLS = 230 V Frequency is f = 60 Hz…
Q: A single-phase two-winding transformer rated 90 MVA, be connected as an autotransformer rated 80/200…
A:
Q: Let a 5-kVA, 400/200-V transformer be approximately represented by a 2-2 reactance referred to the…
A: Equivalent model oftransformer- Since no load current is very small 2 to 5% of full load current. No…
Q: During the load test of single-phase transformer, when the secondary terminal voltage increases, the…
A:
Q: A 400-MVA, 240-kV/24-KV, three-phase Y-A transformer has an equivalent series impedance of 1.2 + j6…
A: According to the question we have to find the line-to-line voltage at high terminals of the…
Q: A 50-kVA 13.8-kV/208-V (rms, line-line) ∆−Ythree-phase distribution transformer has a per-unit…
A: Dear student as per our guidelines we are supposed to solve only one question in which it should…
Q: (b) In a transformer test, data from short circuit and open circuit tests of a 75-kVA, 4600-230V,…
A:
Q: Q2. (a) Explain what is per unit system? What are the advantages of per-unit computations? Prove for…
A: PU system: Per Unit system is a quantity expression system used in an electrical power system which…
Q: The label values of the single-phase transformer whose electrical equivalent circuit is given…
A:
Q: (a) The per unit voltage regulation when the transformer delivers full-load current at a power…
A: A transformer is an electrical machine which is used in AC circuit to either step up or step down…
Q: A 50-kVA 13.8-kV/208-V (rms, line-line) ∆ − Y three-phase distribution transformer has a per unit…
A: Given,High voltage side, line voltage(Base) =13.8 kVApparent power (S)(Base)=50 kVAa) As primary is…
Q: الامتحان العملي لمادة المكائن)الفصل الاول( Q1) Draw the graph of output power versus efficiency of…
A: Since there are multiple questions uploaded so solving the first question accordingly as per the…
Q: Q2. (a) Explain what is per unit system? What are the advantages of per-unit computations? Prove for…
A:
Q: A 400-MVA, 240-kV/24-KV, three-phase Y-A transformer has an equivalent series impedance of 1.2 + j6…
A: Delta-Star transformer- A Delta-Star transformer is a transformer whose primary side is in delta…
Step by step
Solved in 2 steps with 2 images
- Consider the oneline diagram shown in Figure 3.40. The three-phase transformer bank is made up of three identical single-phase transformers, each specified by X1=0.24 (on the low-voltage side), negligible resistance and magnetizing current, and turns ratio =N2/N1=10. The transformer bank is delivering 100 MW at 0.8 p.f. lagging to a substation bus whose voltage is 230 kV. (a) Determine the primary current magnitude, primary voltage (line-to-line) magnitude, and the three-phase complex power supplied by the generator. Choose the line-to-neutral voltage at the bus, Va as the reference Account for the phase shift, and assume positive-sequence operation. (b) Find the phase shift between the primary and secondary voltages.Consider Figure 3.4. For an ideal phase-shifting transformer, the imda nce is unchanged when it is referred from one side to the other. (a) True (b) FalseThree single-phase, two-winding transformers, each rated 450MVA,20kV/288.7kV, with leakage reactance Xeq=0.10perunit, are connected to form a three-phase bank. The high-voltage windings are connected in Y with a solidly grounded neutral. Draw the per-unit equivalent circuit if the low-voltage windings are connected (a) in with American standard phase shift or (b) in Y with an open neutral. Use the transformer ratings as base quantities. Winding resistances and exciting current are neglected.
- For developing per-unit equivalent circuits of single-phase three-winding transformer, a common Sbase is selected for all three windings and voltage bases are selected in proportion to the rated voltage of the windings (a) True (b) FalseA three-phase transformer is rated 1000MVA,220Y/22kV. The Y-equivalent short-circuit impedance, considered equal to the leakage reactance, measured on the low-voltage side is 0.1. Compute the per-unit reactance of the transformer. In a system in which the base on the high-voltage side of the transformer is 100MVA,230kV what value of the per-unit reactance should be used to represent this transformer?A single-phase two-winding transformer rated 90MVA,80/120kV is to be connected as an autotransformer rated 80/200kV. Assume that the transformer is ideal. (a) Draw a schematic diagram of the ideal transformer connected as an autotransformer. showing the voltages, currents, and dot notation for polarity. (b) Determine the permissible kVA rating of the autotransformer if the winding currents and voltages are not to exceed the rated values as a two-winding transformer. How much of the kA rating is transferred by magnetic induction?
- The per-unit equivalent circuit of two transformers Ta and Tb connected in parallel, with the same nominal voltage ratio and the same reactan of 0.1 per unit on the same base, is shown in Figure 3.43. Transformer Tb has a voltage-magnitude step-up toward the load of 1.05 times that of Ta (that is, the tap on the secondary winding of Tb is set to 1.05). The load is represented by 0.8+j0.6 per unit at a voltage V2=1.0/0 per unit. Determine the complex power in per unit transmitted to the load through each transformer, comment on how the transformers share the real and reactive powers.Three single-phase two-winding transformers, each rated 25MVA,54.2/5.42kV, are connected to form a three-phase Y- bank with a balanced Y-connected resistive load of 0.6 per phase on the low-voltage side. By choosing a base of 75 MVA (three phase) and 94 kV (line-to-line) for the high-voltage side of the transformer bank, specify the base quantities for the low-voltage side. Determine the per-unit resistance of the load on the base for the low-voltage side. Then determine the load resistance RL in ohms referred to the high-voltage side and the per-unit value of this load resistance on the chosen base.The ideal transformer windings are eliminated from the per-unit equivalent circuit of a transformer. (a) True (b) False
- Reconsider Problem 3.64 with the change that now Tb includes both a transformer of the same turns ratio as Ta and a regulating transformer with a 4 phase shift. On the base of Ta, the impedance of the two comp onents of Tb is jO.1 per unit. Determine the complex power in per unit transmitted to the load through each transformer. Comment on how the transformers share the real and reactive pors.The leakage reactance of a three-phase, 300-MVA,230Y/23-kV transformer is 0.06 per unit based on its own ratings. The Y winding has a solidly grounded neutral. Draw the per-unit equivalent circuit. Neglect the exciting admittance and assume the American Standard phase shift.The ratings of a three-phase, three-winding transformer are Primary: Y connected, 66kV,15MVA Secondary: Y connected, 13.2kV,10MVA Tertiary: connected, 2.3kV,5MVA Neglecting resistances and exciting current, the leakage reactances are: XPS=0.09 per unit on a 15-MVA,66-kV base XPT=0.08 per unit on a 15-MVA,66-kV base XST=0.05 per unit on a 10-MVA,13.2-kV base Determine the per-unit reactances of the per-phase equivalent circuit using a base of 15 MVA and 66 kV for the primary.